4.6.3 Fixing the damper when a fire batt is used
Horizontal duct
Fig. 36: Fixing of the FKA2-EU with fire batt installation in walls
1
FKA2-EU
2.4
Coated board system
3
Wall, solid wall shown
4.1
Solid ceiling slab
5.4
Threaded rod M12 with washer and nut
5.18
Steel angle section to EN 10056-1,
L ≥ 40 mm
×
40 mm
×
5 mm, galvanised or
painted, or equivalent
9.1
Flexible connector (recommended)
Note:
Each fire damper has to be suspended both on the operating side and on the installation side. The suspension
is carried out in each case above
or
below the flange.
Installation
Fixing the fire damper > Fixing the damper when a fire batt is used
Fire damper Type FKA2-EU
52