2
Technical data
2.1 General data
Nominal sizes B × H
200 × 100 – 1500 × 800 mm *
Casing lengths L
305 and 500 mm
Volume flow rate range
Up to 14400 l/s or 51840 m³/h
Differential pressure range
Up to 2000 Pa
Temperature range
1, 3
-20 °C to 50 °C
Release temperature
72 °C or 95 °C (for warm air ventilation systems)
Upstream velocity
2
≤ 8 m/s with fusible link,
≤ 12 m/s with spring return actuator
Closed blade air leakage
EN 1751, Class 2
Casing air leakage
EN 1751, Class C; (B + H) ≤ 700, Class B
EC conformity
Construction Products Regulation (EU) No. 305/2011
EN 15650 – Ventilation for buildings – Fire dampers
EN 13501-3 – Classification: Fire resistant ducts and fire
dampers
4
EN 1366-2 – Fire resistance tests for installations: Fire
dampers
EN 1751 Ventilation for buildings – Air terminal devices
Declaration of performance
DoP / FKA2-EU / DE / 002
1)
Temperatures may differ for units with attachments. Details for other applications are available on request.
2)
Data applies to uniform upstream and downstream conditions for the fire damper.
3)
Condensation and the intake of humid fresh air have to be avoided as otherwise operation will be impaired or not possible.
4)
Leakage rate of the fire damper system tested at 300 Pa and 500 Pa negative pressure.
*
Technical data
General data
Fire damper Type FKA2-EU
7