5.11.4
Mortar-based installation into a concrete base
Mortar-based installation with concrete base into a solid ceiling slab, upright
Fig. 87: Mortar-based installation with concrete base into a solid ceiling slab, upright
1
FKR-EU
2.3
Concrete base
4.1
Solid ceiling slab
5.22
Steel fabric,
Æ
≥
8 mm, mesh aperture 150 mm,
or equivalent, for number of fixing points see
table
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
Up to EI 120 S
Note:
EI 120 S also for two FKR-EU with spacing of 60 – 225 mm.
Minimum number of fixing points in the bare ceiling
B
A
≥
Æ
315
≥
Æ
500
Æ
800
≥
Æ
315
4
6
8
≥
Æ
500
6
8
10
≥
Æ
800
8
10
12