Mortar-based installation with concrete base into a solid ceiling slab, upright, combined, FKR-EU and FK2-
EU
Fig. 88: Mortar-based installation with concrete base into a solid ceiling slab, upright, combined, FKR-EU and FK2-
EU
1a
FKR-EU
1b
FK2-EU up to B
×
H
≤
800
×
400 mm
2.3
Concrete base
4.1
Solid ceiling slab
5.22
Steel fabric,
Æ
≥
8 mm, mesh aperture 150 mm,
or equivalent, for number of fixing points see
table
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
s2
Spigot construction 40 – 225 mm
Flange construction 80 – 225 mm
Up to EI 90 S
Installation
Solid ceiling slabs > Mortar-based installation into a concrete base
Fire damper FKR-EU