5.13.2
Dry mortarless installation with installation kit TQ into wooden beam ceilings
Dry mortarless installation with installation kit TQ in wooden beam / laminated beam ceiling, upright
Fig. 102: Dry mortarless installation with installation kit TQ into wooden beam / laminated beam ceiling, upright (illus-
tration representative, alternative ceiling construction possible on request)
1
FKR-EU
2.11
Installation kit TQ (factory assembled)
5.1
Dry wall screw
6.5
Mineral wool filling depending on ceiling con-
struction
7.11
Trim panel, same construction as 7.19
7.15
Wood sheet, min. 600 kg/m³
7.16
Wooden beam / gluelam min. 100
×
80 mm
(reduce distances between wooden beams to the
size of the installation opening)
7.17
Trimmers, wooden beam / glued laminated
timber min. 100
×
80 mm
7.19
Fire-resistant cladding (ceiling-dependent)
Z
Spigot construction 370 mm
Flange construction 342 mm
Up to EI 90 S
Up to EI 60 S
EI 30 S
Installation
Wooden beam ceilings > Dry mortarless installation with installation ...
Fire damper FKR-EU
131