Solid wood wall/CLT wall, "flange to flange"
Fig. 70: Mortar-based installation into a solid wood wall or CLT wall, flange to flange, illustration shows side by side
installation (applies also to installation of dampers on top of each other)
1
FKR-EU
2.1
Mortar
3.11
Solid wood wall / CLT wall
4.1
Solid ceiling slab / solid floor
5.13
Wood screw or pin
7.10
Trim panels
7.13a
Cladding, single-layer, fire-resistant
7.14
Reinforcing board of the same material
(required for W < 100 mm, optionally on the
operating or installation side)
Z
Spigot construction 370 mm
Flange construction 342 mm
s2
Spigot construction 40 – 225 mm
Flange construction 80 – 225 mm
*
Installation near the floor analogous to
#
optional
–
Up to EI 90 S
Additional requirements: mortar-based installation
into solid wood walls
Solid wood wall or CLT wall,
Installation
Solid wood walls > Mortar-based installation
Fire damper FKR-EU
94