4.4.2 Assembling AHU casing units
Joining AHU casing units with screws/bolts
NOTICE!
Risk of damage to property from incorrect
assembly!
Be sure to assemble the AHU casing units correctly
as otherwise the condensate drain may be damaged.
–
Protect the condensate drain from damage.
Fig. 16: Joining the base frames with screws/bolts
①
Hexagon head screws
②
Washers
③
Nuts
④
Module connectors
⑤
Allen screws
⑥
Schnorr
®
washers
Screw the AHU casing units evenly to the end
faces of the base frames and to the casing unit
connectors.
Installing AHU casing units on top of each other
Do not start assembling the upper units until you have
completed assembly of the lower units, including screw-
fixing the module connectors and the base frame.
Follow the assembly instructions carefully as otherwise
the unit may become damaged, the casing units may
start shifting or, if the unit is installed outdoors, water
may get into the unit.
Factory drilled holes indicate where the lower and
upper AHU casing units have to be joined. Align and
fix the casing units according to these holes.
Be sure to use all of the fixing points. If an assembly
point is difficult to access, check if it is possible to
assemble the units in a different order.
Ensure that the position is correct based on the
screw joints on the operating side.
Ensure that no water can get into the unit at the fac-
tory provided joints.
If in doubt, consult TROX.
Without intermediate frame
1.
When the installation of the lower casing units is
completed, place the first upper casing unit with
lifting gear, e.g. a crane, in the appropriate instal-
lation position (see enclosed drawing),
port on transport brackets’ on page 18
are several upper AHU casing units, install them
one after another before putting on additional
casing units.
Fig. 17: Removing transport brackets
2.
Remove the transport brackets from the upper
AHU casing unit ( Fig. 17 /1).
3.
If there are several AHU casing units, connect
them together using casing unit connectors,
Setup and assembly
Setting up and assembling the air handling unit > Assembling AHU casing units
Air handling unit X-CUBE X2 / X-CUBE X2 compact
26