1.
Place the noise insulating connector ( Fig. 19 /1) on the air handling unit with the perimeter seal facing down;
fix it with thread forming screws ( Fig. 19 /2), rubber seals ( Fig. 19 /4) and washers ( Fig. 19 /3).
Attaching the noise insulating connector to a multileaf damper
If the noise insulating connector is to be attached to a multileaf damper, fix it with the supplied socket cap
head screws ( Fig. 19 /5), rubber seals ( Fig. 19 /4), washers ( Fig. 19 /3 and 6) and nuts ( Fig. 19 /7).
2.
Fix one eye of the ground cable ( Fig. 19 /8) with a pan head screw M6
×
12 ( Fig. 19 /10) and a serrated lock
washer ( Fig. 19 /9) to the noise insulating connector.
NOTICE!
Electrical conductivity
For electrical conductivity the serrated lock washer needs to be fitted between the eye of the ground cable
and the coated surface.
3.
Fix the other eye of the ground cable with a socket cap head screw M6
×
30 ( Fig. 19 /11) and a serrated lock
washer through the panel sheet to the tubular frame of the air handling unit.
4.4.3 Additional assembly steps for out-
door units
Connecting the roof segments
Air handling units for outdoor installation require the fol-
lowing additional assembly steps:
Fig. 20: Joining roof segments
①
Roof segments
②
Self-adhesive joint sealing tape
③
Cover strips
④
Self-drilling screws with sealing washers
1.
Seal all joints between the roof segments
( Fig. 20 /1) with self-adhesive joint sealing tape
( Fig. 20 /2). Follow the tape manufacturer's
instructions for use. Attach the cover strips
( Fig. 20 /3) and fix them with self-drilling screws
NOTICE!
Remove the eye nuts where the casing units
are to be joined such that you can actually join
the roof segments. Do not remove the other
eye nuts; they have to remain in place to pre-
vent the ingress of rain into the unit.
Fig. 21: Sealing the joints
2.
Seal the joints ( Fig. 21 /1) between the cover
strips with the supplied adhesive strips
(100 x 40 mm).
Make sure that all surfaces are clean, free from
grease, and dry. Clean the surfaces, if necessary.
Setup and assembly
Setting up and assembling the air handling unit > Additional assembly steps for outdoor units
Air handling unit X-CUBE X2 / X-CUBE X2 compact
29