12
TN19 121211-20
Note: See "Combustion Air" section on page 9.
1. Position stove and fl oor protection with hole for com-
bustion air in accordance with the clearances as stated
on the label and in Figure #1. or #2
2. Mark the position for the hole in the ceiling and roof
by using a string and plumb-bob.
3. Check that the intended location will not interfere with
fl oor joists, ceiling joists or rafters before proceeding
further.
4. Cut a hole in the ceiling and roof to suit the chimney
system and frame in the sides. The chimney support is
mounted to the framing.
5. Assemble chimney sections so the fi nished length is
resting on the support and protruding through the roof.
Avoid having joints between ceiling and roof. Install
radiation shield. Assemble fl ashing and storm collar and
be sure to maintain the vapour barrier at this point. (Seal
securely.) Attach rain cap and check fl ashing for leaks.
6. Install connector as per manufacturer's instructions.
7. Attach stove to fl oor using two 1/4" x 1" or longer lag
screws.
8. If installing a leg model, insert anchor tabs into slot
on bottom of two rear legs and secure to fl oor with 1/4"
x 1" or longer lag screws. Fig. #3a
Mobile Home
Installation
Warning: Under no circumstances is this heater to
be installed in a makeshift or "temporary" manner. It
may be fi red only after the following conditions have
been met.
- DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
- DO NOT INSTALL IN A SLEEPING ROOM.
- Outside air supply must be used for Mobile Home
instalations see Figure #3, Page 11.
Clearances
This heater must be installed with listed double-wall connec-
tor and compatible chimney system listed on page 11.
Clearances to combustible surfaces and materials are
shown in Figure #1, page 6 and Fig #2, Page 7.
Clearances may be reduced with various heat insulating
materials. Consult local fi re codes and authorities for
approval.
Chimney Installation
This room heater should be connected to a 6" factory
built chimney conforming to CAN/ULC-S629, Stand-
ard for 650 degrees Celsius factory built chimneys.
Minimum chimney height from fl oor is 12' (3.66m) or
as per chimney manufacturers roof clearances.
NOTE:
Longer chimney lengths and different pitch fl ashings
may be used. All other parts listed must be installed (see
Figure #4, Page 13). Install all components to the connec-
tor or chimney manufacturer's installation requirements.
Consult your chimney supplier for installation advice.
Procedure:
WARNING: THE STRUCTURAL INTEGRITY OF THE MOBILE
HOME FLOOR, WALL AND CEILING/ROOF MUST BE
MAINTAINED.
NATIONAL
FIREPLACE
INSTITUTE
CERTIFIED
www.nficertified.org
We recommend that our products be
installed and serviced by professionals
who are certified in the U.S. by the
National Fireplace Institute (NFI)
or in Canada by Wood
Energy Technical
Training (WETT)
Wood Energy
Technical Training
www.wettinc.ca
FIG. #3a