Wire Gauge for 2% Voltage Drop in Supply Circuits
115 Volt
Distance In Feet To Center of Load
Amps
20 30 40 50 60 70 80 90 100 120 140 160
2
14
14
14
14
14
14
14
14
14
14
14
14
3
14
14
14
14
14
14
14
14
14
14
14
12
4
14
14
14
14
14
14
14
14
14
12
12
12
5
14
14
14
14
14
14
14
12
12
12
10
10
6
14
14
14
14
14
14
12
12
12
10
10
10
7
14
14
14
14
14
12
12
12
10
10
10
8
8
14
14
14
14
12
12
12
10
10
10
8
8
9
14
14
14
12
12
12
10
10
10
8
8
8
10
14
14
14
12
12
10
10
10
10
8
8
8
12
14
14
12
12
10
10
10
8
8
8
8
6
14
14
14
12
10
10
10
8
8
8
6
6
6
16
14
12
12
10
10
8
8
8
8
6
6
6
18
14
12
10
10
8
8
8
8
8
8
8
5
20
14
12
10
10
8
8
8
6
6
6
5
5
25
12
10
10
8
8
6
6
6
6
5
4
4
30
12
10
8
8
6
6
6
6
5
4
4
3
35
10
10
8
6
6
6
5
5
4
4
3
2
40
10
8
8
6
6
5
5
4
4
3
2
2
45
10
8
6
6
6
5
4
4
3
3
2
1
50
10
8
6
6
5
4
4
3
3
2
1
1
Wire Gauge for 2% Voltage Drop in Supply Circuits
230 Volts
Distance In Feet To Center of Load
Amps
20 30 40 50 60 70 80 90 100 120 140 160
5
14
14
14
14
14
14
14
14
14
14
14
14
6
14
14
14
14
14
14
14
14
14
14
14
12
7
14
14
14
14
14
14
14
14
14
14
12
12
8
14
14
14
14
14
14
14
14
14
12
12
12
9
14
14
14
14
14
14
14
14
12
12
12
10
10
14
14
14
14
14
14
14
12
12
12
10
10
12
14
14
14
14
14
14
12
12
12
10
10
10
14
14
14
14
14
14
12
12
12
10
10
10
8
16
14
14
14
14
12
12
12
10
10
10
8
8
18
14
14
14
12
12
12
10
10
10
8
8
8
20
14
14
14
12
10
10
10
10
10
8
8
8
25
14
14
12
12
10
10
10
10
8
8
6
6
30
14
12
12
10
10
10
8
8
8
6
6
6
35
14
12
10
10
10
8
8
8
8
6
6
5
40
14
12
10
10
8
8
8
6
6
6
5
5
50
12
10
10
8
6
6
6
6
6
5
4
4
60
12
10
8
6
6
6
6
6
5
4
4
3
70
10
10
8
6
6
6
5
5
4
4
2
2
80
10
8
8
6
6
5
5
4
4
3
2
2
90
10
8
6
6
5
5
4
4
3
3
1
1
100
10
8
6
6
5
4
4
3
3
2
1
1
CONDUCTORS AND CIRCUITS