background image

 

  13 

Hose clips SC (part no. 40712-01) are suitable for fastening the pipes 

(hoses) to walls or the floor. These hose clips also make it possible to 

route water pipes (hoses) on the heater‘s warm

-air distribution pipes 

as a way to avoid the danger of frosting. 

A water pipe (hose) may only be fitted at a clearance of 1.5 m to the 

heater on the warm air duct. The Truma hose clip SC can be used if 
this distance is observed. In the case of parallel installations, e.g. 
openings through a wall, a spacer element should also be attached 
(e.g. insulation) to prevent contact. 

Connect cold water supply (23) to safety/drain valve (24). To 

guarantee the correct function of the safety/drain valve, the water 
pipes/hoses need to be installed without tension! 

Fig. 25 

The elbow fitting (28 

 with aeration valve) is inserted into the upper 

warm water connection and the second elbow fitting (27) is inserted 
in the lower cold water connection of the heater up to the stop. Pull 
in  opposite  direction  in  order  to  make  sure  the  elbow  fittings  are 
securely attached. 

Create a pipe/hose connection (25) for the cold water supply 

between the safety/drain valve (24) and the boiler intake. 

Ensure that the cold water supply does not come into contact 
with cold bridges (e.g. the outer wall) in order to  

prevent freezing. 

Route the hot water supply (26) from the elbow connec tion with 

integrated vent valve (28) to the hot water consumers. 

Push the venting hose, external diameter 11 mm (29), onto the hose 

grommet of the venting valve (28a), and lay it to the outside without 
any kinks. Ensure that the bend radius is not smaller than 40 mm. 

Cut off the aeration hose about 20 mm below the vehicle floor at a 

45° angle to the direction of travel (see figure 25). 

Installing the room temperature sensor 

When selecting the location, bear in mind that the room 

temperature sensor must not be subjected to any direct radiant 
heat. For optimum room temperature regulation, we recommend 
that the room temperature sensor be fitted above the entrance 
door. 

 

Fig. 26 

Please ensure that the room temperature sensor is always 
attached to a 

vertical

 wall. There may be no ob- 

structions preventing the room air from flowing around it. 

Drill a hole 10 mm in diameter. Guide the connection cable through 

the drillhole from behind and plug the cable end to the sensor by 
means of an insulated connector plug (there is no need to be 
concerned about polarity). Slide in the room temperature sensor 
and lay the cable end with the two insulated connector plugs to the 
electronic control unit (extend to a maximum overall length of 10 
m using 2 x 0.5 mm² cable if necessary). connected, otherwise the 
heater will switch to fault. 

 

The provided room temperature sensor 

must always be  

Installing the control panel 

The installation of the control panel is described in the instructions 

included with the control panel. 

Electrical connections 

Route connecting cables in such a way that they cannot chafe. 

Please also use leadthrough bushings or edge protection profiles 
where there are sharp edges such as metal panel leadthroughs. The 
connecting cables must not be attached to or come into contact 
with metal surfaces, the exhaust duct or warm air ducts. 

The electrical connections are located under the connection cover 

(39). The cover can be removed by pressing and  simultaneously 
sliding it in the direction of the arrow. When removing or 
installing the connection cover on the connection cables, make 
sure that the cables are not pulled out or  become pinched. 

 

40

 

42 

44 

46 

48

 

 

41

 

43 

45 

47

 

Fig. 27 

40 = Input v12 V (spade connector 6.3 mm) 41 = 

Input voltage -12 V (spade connector 6.3 mm) 

42

 

= not used 

43

 

= Device fuse: 10 A 

 slow 

 (T 10 A) 

44

 

= Wire bridge (or window switch 

 accessory) 

45

 

= not used 

46

 

= Room temperature sensor 

47

 

= Control panel / Diagnostic connector* 

48

 

= Control panel / Diagnostic connector* 

*  Alternative connections. 

All connections to the unit should be made with sagging  connection 

cables. This will prevent condensation water from running down the 
connection cables and into the unit. 

 

 

 

 

 

 

Summary of Contents for Combi 2E CP plus

Page 1: ...Combi 2 E 4 E CP plus Australia Operating instructions Page 2 Installation instructions Page 9 To be kept in the vehicle...

Page 2: ...ion 5 Gas connection with pressure test point not shown 6 Hot air outlets 7 Recirculated air intake 8 Waste gas discharge 9 Combustion air infeed 10 Electronic control unit 11 Water container 10 litre...

Page 3: ...unit gas mode only LPG for autonomous use electrical mode only 240 V for stationary use on camp sites or gas and electrical mode mixed mode Only possible in heating and hot water mode Heating and hot...

Page 4: ...essure control systems DuoControl CS for dual cylinder gas systems At temperatures of around 0 C or less the gas pressure regulator and the changeover valve should be operated using the EisEx regulato...

Page 5: ...er that has frozen The boiler can be thawed out again by briefly starting it up max 2 minutes Frozen lines can be thawed out by heating up the interior If connected to a central water supply rural or...

Page 6: ...switch If the 12 V power supply is interrupted during operation or during the after run period for example the temperatures within the unit could activate the overheating protection Fig 6 To reset th...

Page 7: ...Dimensions Fig 7 The right to effect technical modifications is reserved Truma warranty policy Truma CP plus The warranty is given by Dometic Pty Ltd Building 3B Digital control panel Truma CP plus pa...

Page 8: ...s Apart from any warranties implied by the Trade Practices Act 1974 or any relevant State legislation all other warranties express or implied whether arising by virtue of statute or otherwise are here...

Page 9: ...on with the original Fig 9 In order to heat the vehicle evenly throughout the heater must be installed in a location in the vehicle that is as central as possible in a wardrobe stowage compartment or...

Page 10: ...e heating device assembly instructions are enclosed with the delivery Installing the wall cowl Permissible duct lengths The length specific ations refer to the combusti on air intake duct Ducts with a...

Page 11: ...et of the unit in confined spaces we recommend the use of the BGC 90 elbow part no 34091 01 This elbow makes it possible to connect a R warm air duct with a diameter of 65 mm or a VR warm air duct wit...

Page 12: ...s 27 28 and safety drain valve 24 have a 12 mm rigid piping connection e g John Guest System For connecting to rigid pipes with other diameters appropiate adapters not included in scope of delivery mu...

Page 13: ...e regulation we recommend that the room temperature sensor be fitted above the entrance door Fig 26 Please ensure that the room temperature sensor is always attached to a vertical wall There may be no...

Page 14: ...from Truma for the different applications Please ask your dealer Other chargers may be used only with a 12 V battery as a buffer Room temperature sensor Attach plug of connecting cable to connection 4...

Page 15: ...Dometic Service C entre if problems are encountered in other countries the relevant service partners should be contacted www truma com Having the e quipment model and the serial number ready see type...

Page 16: ...Road Clayton Victoria 3168 Australia Service Australia Telephone 61 0 3 92 39 10 50 Facsimile 61 0 3 92 39 10 99 Dometic New Zealand Ltd Post Box 12011 1642 Penrose Auckland New Zealand Service New Z...

Reviews: