7.
Operation
7.1
Commissioning
Performing initial commissioning
Conditions
■
PC on which one of the following browsers is installed:
−
Microsoft Internet Explorer from version 11.
−
Microsoft Edge.
−
Google Chrome from version 46.
−
Firefox from version 40.
■
Ethernet cable for connecting PC and TruConvert Sys-
tem Control.
The initial commissioning of the device is only possible via the
web-based user interface.
1. Set the same IP Subnet Mask on the PC as on the TruCon-
vert System Control.
IP Subnet Mask of the TruConvert System Control on deliv-
ery: 255.255.255.0
2. Set the same address range on the PC as on the TruCon-
vert System Control:
192.168.1.-
3. On the PC, set the last block of the IP address.
Do not set the same address as on the TruConvert Sys-
tem Control!
IP address of the TruConvert System Control on delivery:
192.168.1.2
Do not set
0
!
4. Connect PC and TruConvert System Control with Ethernet
cable.
5. To switch on the system control and the AC-DC module:
switch on the 24 V supply voltage.
All 3 status LEDs flash to display the "Initialization" state.
6. Open the web browser on the PC.
7. Enter IP address of the TruConvert System Control in the
address line.
IP address of the TruConvert System Control on delivery:
192.168.1.2
A67-0141-00.BKEN-
001-05
2020-06-10
Operation
41
Establishing and testing the
connection