Ø
To set the set values for a single DC-DC module: Enter
the number of the slave in the "Slave Module Selection"
area under "Slave Number".
The number of available DC-DC modules is displayed in
"Available Slave Modules".
The DC-DC module, which is directly connected to the
system control with the data cable, is "Slave Number" =
1. The next DC-DC module, which is connected to data
output "OUT" of slave 1, is "Slave Number" = 2. The DC-
DC module connected to this is "Slave Number" = 3 etc.
or
Ø
To uniformly set the set values for all DC-DC modules:
set the "Slave Number" = 0.
15. For "DC Voltage Limits", enter:
−
"Minimum Battery Voltage [V]": lower limit, up to which
the battery is discharged.
Upon reaching the limit value, the discharging current is
reduced.
−
"Maximum Battery Voltage [V]": upper limit, up to which
the battery is charged.
Upon reaching the limit value, the charging current is
reduced.
16. Enter the limit values for the DC-DC module in the "DC Volt-
age Alarm Thresholds" area:
−
"Minimum Battery Voltage Threshold [V]": lower limit, up
to which the battery is discharged.
If this value is not met (e.g., due to short circuit of the
battery), the TruConvert System Control generates an
alarm message.
−
"Maximum Battery Voltage Threshold [V]": upper limit, up
to which the battery is charged.
If the value is exceeded, the TruConvert System Control
generates an alarm message.
−
Select the values so that they lie outside of the "DC Volt-
age Limits" control range.
The difference between Minimum Battery Voltage [V] and
Minimum Battery Voltage Threshold [V] should be 5 V. A
smaller difference is possible as well but may result in
shutdowns.
17. Enter limit values for the charging and discharging current in
the "DC Current Settings" area:
−
"Maximum Battery Charge Current [A]": maximum battery
charging current.
−
"Maximum Battery Discharge Current [A]": maximum bat-
tery discharging current
18. Enter limit value for the power output/power draw in the "DC
Power Settings" area:
−
"Maximum Terminal Power [W]": maximum power.
7
‐
6
Commissioning
2020-07-01
A67-0140-00.BKen-0
01-05
Summary of Contents for TruConvert DC 1000 Series
Page 1: ...Operator s manual TruConvert DC series 1000 TruConvert System Control TruConvert Modular...
Page 2: ......
Page 6: ...II Good to know 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 36: ...3 12 Technical data dependent on device variant overview 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 38: ...7 Ethernet 4 10 8 RS 485 4 11 4 2 Interfaces 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 40: ...Fig 4 3 4 4 Protective earth TruConvert DC series 1000 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 48: ...4 12 RS 485 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 54: ...5 6 CSA certification 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 106: ...16 State diagram State machine Fig 7 19 7 38 State diagram 2020 07 01 A67 0140 00 BKen 0 01 05...