4.
Transmission of power
4.1
Switching the transmission of power
on/off
Conditions
■
Initial commissioning was performed
.
■
Operation via web-based user interface or Modbus.
1. Selection of a DC-DC module (only relevant if multiple mod-
ules are connected to a TruConvert System Control).
−
User interface:
Select >
Operation
>
Device Control DC-DC
.
Select a module in the "Device Control DC-DC" area for
"Slave Module Selection".
−
Modbus:
Enter the number of the slave to be addressed
.
Note
User interface and Modbus have different scaling.
For example:
100 A/ms = 100 on user interface = 10000 in Modbus.
2. Enter set value for the battery current in A.
Charge battery:
enter negative value.
Discharge battery:
enter positive value.
−
User interface:
Under "Set Value Battery Current [A]", enter the value.
−
Modbus:
.
3. Enter maximum allowed battery current change in A/ms.
−
User interface:
Under "Battery Current Slope [A/ms]", enter the value.
−
Modbus:
.
4. Start transmission of power.
7
‐
16
Transmission of power
2020-07-01
A67-0140-00.BKen-0
01-05
Enter process set values
Start transmission of power
Summary of Contents for TruConvert DC 1000 Series
Page 1: ...Operator s manual TruConvert DC series 1000 TruConvert System Control TruConvert Modular...
Page 2: ......
Page 6: ...II Good to know 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 36: ...3 12 Technical data dependent on device variant overview 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 38: ...7 Ethernet 4 10 8 RS 485 4 11 4 2 Interfaces 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 40: ...Fig 4 3 4 4 Protective earth TruConvert DC series 1000 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 48: ...4 12 RS 485 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 54: ...5 6 CSA certification 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 106: ...16 State diagram State machine Fig 7 19 7 38 State diagram 2020 07 01 A67 0140 00 BKen 0 01 05...