Attaching Capture Hood to Stand 

1.

 

Mount the capture hood base onto the quad 

bracket corners. Use thumbscrews to tighten. 

2.

 

Raise the hood using the adjustable extension 

poles. 

3.

 

Make sure to make a tight seal against the outlet. 

4.

 

Lock in place by tightening the thumbscrews on 

the extension poles. 

Taking Flow Measurements 

Flow measurement readings can easily be viewed directly on the large backlit display, or by utilizing the 

following innovative, productivity enhancements: 

LogDat

™ 

Mobile Remote Reader and Data Logger Software

 

 

Utilizing wireless Bluetooth

®

 technology, this app for Android™-

based smartphones and tablets communicates with the instrument 

remotely over 100 ft. (30.5 m) away and displays sample data in 

real time. Attach comments, voice notes, and photos to test ID data 

for export via email to generate reports. 

 

Detach Micromanometer from the Base and Connect Directly to the 

Flow Manifold  

 

Disconnect short tubing from the ports on the flow manifold  

 

Use the two 8 ft. (2.4 m) sections of tubing included with the instrument 

o

 

Connect one section of tubing to the “

+

” port on the micromanometer, 

and the other end to the flow manifold port facing towards the top of 

the hood. 

o

 

Connect the other section of tubing to the “

-

” port on the 

micomanometer, and the other pressure port on the flow manifold. 

 

Program temperature into micromanometer 

o

 

Go to “

Actual/Std Setup

” menu  

o

 

Set “

Temp Source

” to “

Entered

” 

o

 

Enter ambient temperature 

 

Disable “

Headphone Input

” 

o

 

Go to “

Settings

” menu 

o

 

Set to “

Disable

” 

 

 

Notes 

When using the stand: 

 

Backpressure compensation mode cannot be utilized. 

 

Make sure the backpressure flap on the base is in the open position. 

 