OPERATOR’S MANUAL
ISO
6
Version 4 UL 2_3 Manual
DIAGNOSTICS / 199
6011258 Rev C
-
The Diagnostics screen will show Channel 1 as
a default.
-
If a channel other than Channel 1 needs selected, press
the Down button until the appropriate channel displays.
The Down button only displays when more than one
channel is configured.
4. Set the master switch to the ON position or press the
START
button.
5. Make sure the implement is down.
6.
Press the Increment button to open the channel’s valve. The
Channel Pulse Width Modulation (PWM) data item displays
the current PWM signal that is output to the valve.
-
The Increment button must be pressed repeatedly to
increase the PWM signal to the valve. Each press will
increase the signal by 2% PWM. The Channel Pulse
Count and Channel Frequency Filter values display the
current output of the feedback sensor.
7. Press the Decrement button to decrease the PWM signal
and close the valve. The Decrement button must be pressed
repeatedly to decrease the PWM signal to the valve. Each
press decreases the signal by 2% PWM.
-
The active channel displays in the button text.
8. Turn the master switch off to shutdown control channel or
press the
STOP
button.
9. Press the Home button and select the
CONTROLS
button to
reset Control Mode to Auto.