Solenoid Voltage Alarm
Solenoid voltage is below 11V or higher
than 16V.
1.
Damaged CAN or module harness.
2.
Blown module harness fuse.
3.
Defective module.
1.
Inspect CAN/module harness of
the identified module for damage.
Repair or replace harness.
2.
Inspect module harness fuse
or replace.
3.
Inspect identified module for damage
or replace.
606
Ground Offset
Voltage Alarm
The ground offset is below -2V or above 2V.
1.
Damaged/shorted Actuator Harness.
2.
Defective PWM valve driver or
Servo valve driver.
3.
Defective module.
1.
Inspect Actuator Harness for
damage around the WPM and
Servo valve connections. Repair or
replace harness.
2.
Inspect PWM or Servo valve drivers
for damage and replace if necessary.
3.
Inspect identified module for
damage and replace if necessary.