The lamp lights during normal monitoring conditions and turns 

                                              off during Shock Relay output. 

 

OC 

䞉䞉䞉䞉䞉䞉䞉䞉䞉䞉

The lamp lights when present current exceeds set level. 

 

DIP Switch

 

䞉䞉䞉䞉䞉䞉䞉

Select Shock Relay output mode.   

SS

Normal / excitation, self-hold after trip.

 

SA

Normal / No excitation, automatically reset after trip. 

To convert DIP stitch, open with miniature driver from the left side of cover. 
Note

Power off when convert DIP switch. 

Current  

䞉䞉䞉䞉

Current setting knob 

Start Time 

䞉䞉䞉䞉

Start time setting knob

Mon and OC lamps flicker during start 

time.

   

Shock Time

䞉䞉䞉

Shock time setting knob 

TEST

㻌 䞉䞉䞉䞉䞉䞉䞉䞉

Test Shock Relay operation. To test, press and hold the TEST button       

longer than the set START TIME or SHOCK TIME. 

To check SHOCK TIME, minimalize START TIME; to check START 
TIME, minimalize SHOCK TIME.   

㻌 㻌 㻌 㻌 㻌

Note) Output relay works by pressing TEST button when motor stops. 

                            (Output relay doesn’t work when motor is running. ) 

Reset

 

䞉䞉䞉䞉䞉䞉䞉

  Reset Shock Relay after trip.

Only works with DIP Switch SS

䠅㻌

 

 
 
 
 
 
 
 
 
 
 
 
 

 

Note

Shock Relay output mode varies with DIP switch selection. 

䠍䠎䠊

Basic Function 

A

Current (Operation current value) Factory default setting

MAX

fully rihgt

 

When the motor current exceeds the present CURRENT value, Shock Relay detects the  overload 
and trips.   

B

Start Time (Start prohibiting time) Factory default setting

MIN

fully left

 

When the motor starts, there is a possibility that the motor current will exceed the set current 
value. To prevent Shock Relay from tripping due to the spike in start current,  start time is set a 
little longer than motor startup period.   

When overload takes place in the motor startup, Shock Relay trips after the total time of start 

time and shock time lapse.   

C

Shock Time (Continuous overload time) Factory default setting

MIN

fully left

 

When instantaneous overload occurs, motor current may exceed current set value. Shock time is 
set to not activate at instantaneous overload.   

Startup 

Motor rotation speed 

Trip 

Motor load current 

Loa

d

 

Time 

 

Current 

Overload 

Motor stop 

Instantaneous overload 

 Start time   

 

Shock time 

 

Shock time 

Set value 

Operation power   

MAX0.5s

 

Relay output SA 

Reset after 
1 second 

Self-hold

 

Relay output SS 

Summary of Contents for TSBSB Series

Page 1: ...WKLV 6 2 5 3OHDVH PDNH VXUH WKDW WKLV LQVWUXFWLRQ PDQXDO DFFRPSDQLHV WKH 6 2 5 WR WKH HQG XVHU 3OHDVH NHHS WKLV LQVWUXFWLRQ PDQXDO VDIH XQWLO WKLV SURGXFW LV GLVSRVHG RI 3URGXFW VSHFLILFDWLRQ LV VXEM...

Page 2: ...Shock Relay Instruction Manual Model Identification Following 3 models include main body and external CT TSBSB100 TSBSB05 Main body TSB2CT100 External CT TSBSB200 TSBSB05 Main body TSB2CT200 External...

Page 3: ...and protective equipment When carrying out operation test or periodic inspection make sure protective device functions properly Megger testing is conditional must be performed in accordance with inst...

Page 4: ...3 TSBSB05 TSBSB10 TSBSB30 TSBSB60 TSBSB100 TSBSB200 TSBSB300 CT and main unit is wired before shipment Mounting hole dimension Install with 35mmDIN rail or mounting plate Screw Cover Mounting hole...

Page 5: ...less Insulation Between casing and circuit Over 10M DC500V Megger Dielectric Strength Between casing and circuit AC2000V 60Hz 1min Between contacts AC1000V 60Hz 1min Between circuits and contacts AC2...

Page 6: ...nstall an isolation transformer Remove terminal cover and use crimp terminal to connect terminal block and wire When connecting without crimp terminal tightening torque of 0 4 0 6N m is recommended to...

Page 7: ...elect Shock Relay and the number of wires pass through according to set current values Main unit alone AC200VMotor AC400VMotor Capacity kW Motor Rate Current A Shock Relay No of wires that pass throug...

Page 8: ...hole 15 55 TSBSB100 1 18 5 67 TSBSB100 1 22 78 TSBSB200 1 30 107 TSBSB200 1 54 TSBSB100 1 37 132 TSBSB200 1 66 TSBSB100 1 45 160 TSBSB300 1 80 TSBSB100 1 55 198 TSBSB300 1 99 TSBSB200 1 75 270 TSBSB30...

Page 9: ...ity of the electromagnetic contactor MC which output contact opens and closes should be less than 200VA when throwing and less than 20VA when holding Part Names SHOCK TIME Shock time setting knob OC O...

Page 10: ...Shock Relay output mode varies with DIP switch selection Basic Function A Current Operation current value Factory default setting MAX fully rihgt When the motor current exceeds the present CURRENT va...

Page 11: ...ting Trouble Check Result Solution Mon does not light A1 A2 wiring Incorrect wiring Wire correctly A1 A2 voltage Not between 24 240V Supply 24 240V Does not trip at current knob MIN Wiring of CT Incor...

Page 12: ...provided in the manual the Seller will repair and replace at no charge once the Goods are returned to the Seller This warranty does not include the following 1 Any costs related to removal of Goods f...

Reviews: