9
䐟
MON
䞉䞉䞉䞉䞉䞉䞉䞉䞉䞉
The lamp lights during normal monitoring conditions and turns
off during Shock Relay output.
䐠
OC
䞉䞉䞉䞉䞉䞉䞉䞉䞉䞉
The lamp lights when present current exceeds set level.
䐡
DIP Switch
㻌
䞉䞉䞉䞉䞉䞉䞉
Select Shock Relay output mode.
SS
䠖
Normal / excitation, self-hold after trip.
㻌
SA
䠖
Normal / No excitation, automatically reset after trip.
To convert DIP stitch, open with miniature driver from the left side of cover.
Note
䠅
Power off when convert DIP switch.
䐢
Current
䞉䞉䞉䞉
Current setting knob
䐣
Start Time
䞉䞉䞉䞉
Start time setting knob
䠄
Mon and OC lamps flicker during start
time.
䠅
䐤
Shock Time
㻌
䞉䞉䞉
Shock time setting knob
䐥
TEST
㻌 䞉䞉䞉䞉䞉䞉䞉䞉
Test Shock Relay operation. To test, press and hold the TEST button
longer than the set START TIME or SHOCK TIME.
To check SHOCK TIME, minimalize START TIME; to check START
TIME, minimalize SHOCK TIME.
㻌 㻌 㻌 㻌 㻌
Note) Output relay works by pressing TEST button when motor stops.
(Output relay doesn’t work when motor is running. )
䐦
Reset
㻌
䞉䞉䞉䞉䞉䞉䞉
Reset Shock Relay after trip.
䠄
Only works with DIP Switch SS
䠅㻌
㻌
Note
䠅
Shock Relay output mode varies with DIP switch selection.
䠍䠎䠊
Basic Function
A
Current (Operation current value) Factory default setting
㸸
MAX
㸦
fully rihgt
㸧
When the motor current exceeds the present CURRENT value, Shock Relay detects the overload
and trips.
B
Start Time (Start prohibiting time) Factory default setting
㸸
MIN
㸦
fully left
㸧
When the motor starts, there is a possibility that the motor current will exceed the set current
value. To prevent Shock Relay from tripping due to the spike in start current, start time is set a
little longer than motor startup period.
䠆
When overload takes place in the motor startup, Shock Relay trips after the total time of start
time and shock time lapse.
C
Shock Time (Continuous overload time) Factory default setting
㸸
MIN
㸦
fully left
㸧
When instantaneous overload occurs, motor current may exceed current set value. Shock time is
set to not activate at instantaneous overload.
Startup
Motor rotation speed
Trip
Motor load current
Loa
d
Time
㻭
Current
Overload
Motor stop
Instantaneous overload
㻮
Start time
㻯
Shock time
㻯
Shock time
Set value
Operation power
MAX0.5s
Relay output SA
Reset after
1 second
Self-hold
Relay output SS