TSURUGA ELECTRIC CORPORATION
■
Connections
Measuring input terminals of the instrument and,
the contact output and auxiliary supply terminals M3.
Make firm and correct connections with crimp type terminal.
Optimum torque of the terminal screws: 0.36~0.48N
・
m
Note :
In case that the model name is NRC-100H, no contact output
terminals for the low limit is provided.
●
Measuring Input Terminals
Arrange a cabling of measuring input line and power source line as
distant as possible from each other. Close and parallel wiring of these
two lines may cause unstable reading of the instrument.
①
DC Volt Meter
DC Current Meter
Receiving Meter
Connect the measuring input with correct polarity.
Use the particular accessory when it is designated.
②
AC Volt Meter
AC Current Meter
Connect the measuring input.
Use the particular accessory when it is designated.
●
Auxiliary supply Terminals
①
AC power source model
②
DC power source model
Connect the AC voltage to the respective terminals of
Connect the DV24V to the auxiliary supply
auxiliary supply terminals (SOURCE).
terminals (SOURCE) with correct polarity.
AC100V power source voltage: Terminals
±
and 100/110V
AC200V power source voltage: Terminals
±
and 200/220V
●
High Limit (HIGH) and Low Limit (LOW) Contact Output Terminals
The contact capacity of high and low limit contact output is, with resistive load: AC250V, 3A or DC30V, 3A
Make the connections with the cable conforming to these capacities. In case that the relay controls with the capacity higher than
these, provide the auxiliary relay externally.
HIG
H
LO
W
M
SOURC
E
a
c
b
a
c
b
Output terminal
[Note]
low limit contact
Output terminal
high limit contact
Measuring
input terminal
supply terminals
Auxiliary
AC INPUT
IN
PU
T
A
C
M
(-)
M
(+
)
(-
)
(+)
SOU
RCE
200V(220V)±10%
100V(110V)±10%
±
SOUR
CE
DC24V±10%
+
-