Connecting the cabtyre cable
Before connecting leads to the terminals, make certain the power supply
is turned off (circuit breaker, etc.), to avoid electrical shock, shorting, or
unexpected starting of the pump, leading to injury.
WARNING
Cabtyre cable
• If it is necessary to extend the cabtyre cable, use a core size equal to
or larger than the original. This is necessary not only for avoiding a
performance drop, but to prevent cable overheating which can result in fire,
electrical leakage or electrical shock.
• If a cable with cut insulation or other damage is submerged in the water,
there is a danger of water seeping into the motor causing a short. This may
result in damage to the pump, electrical leakage, electrical shock, or fire.
• Be careful not to let the cabtyre cable be cut or become twisted. This may
result in damage to the pump, electrical leakage, electrical shock, or fire.
• If it is necessary to submerse the connection leads of the cabtyre cable
in water, first seal the leads completely in a molded protective sleeve, to
prevent electrical leakage, electrical shock, or fire.
Do not allow the cabtyre cable leads to become wet.
Make sure the cable does not become excessively bent or twisted, and does not rub against a structure in a
way that might damage it.
CAUTION
Grounding
Do not use the pump without first grounding it properly. Failure to ground it
can lead to electrical shock from an electrical leak or pump malfunction.
Do not attach the grounding wire to a gas pipe, water pipe, lightening arrestor
or telephone grounding wire. Improper grounding can result in electrical
shock.
WARNING
CAUTION
Electrical circuit diagrams
Red
Red
White
White
White
Black
Black
Green
Yellow
Yellow
U
1
V
1
W
1
S
2
U
2
V
2
W
2
S
1
G S
3
Miniature Protector
Coil
Protector Circuit
Leak Sensor
Power · Control Cable
Power Cable
Star-delta start
Do not use the pump if the cabtyre cable is worn or damaged, which can
result in electric shock, shorting, or fire.
Connect the leads of cabtyre cable to the control panel terminals as shown in the diagram, being careful not
to let the leads become twisted together.
CAUTION
U
1
V
1
W
1
U
2
V
2
W
2
S
3
S
1
G S
2
U
1
-Red
V
1
-White
U
2
-Black
W
1
-Black
Protector Circuit(Yellow)
Leak Sensor Circuit(White)
Protector Circuit(Yellow)
W
2
-White
V
2
-Red
G-Green
Star-delta start