920.1020.15
29
APPENDIX
- WIRING DIAGRAMS
LOW ENERGY APPLICATION: PUSH PLATES WITH APPROACH SIDE DOOR-MOUNTED SENSOR
•
Non-Swing Side (approach) door-mounted sensor is wired into the secondary activation input (13)
at the SW19 I/O board. It is a normally closed circuit.
•
Door-mounted sensor will cause re-activation when in detection during the closing cycle.
•
Secondary activation input is disabled at the full closed door position.
•
Jumpers must be installed between terminal 8 and 12 & 14 if those inputs are not required for the
application. If they are used for the application, they must be connected to a N.C. circuit.