3-6. Operating Mode Description 

Operating mode  Description 

LCD display   

Online mode 

When the input voltage is within 
acceptable range, UPS will provide pure 
and stable AC power to output. The UPS 

will also charge the battery at online 
mode.   

 

ECO mode 

Energy saving mode:   
When the input voltage is within voltage 
regulation range, UPS will bypass 

voltage to output for energy saving.   

 

Frequency 

Converter mode 

When input frequency is within 40 Hz to 

70 Hz, the UPS can be set at a constant 
output frequency, 50 Hz or 60 Hz.    The 
UPS will still charge battery under this 

mode. 

 

Battery mode 

When the input voltage is beyond the 

acceptable range or power failure and 
alarm is sounding every 4 second, UPS 
will backup power from battery.   

 

Bypass mode 

When input voltage is within acceptable 
range but UPS is overload, UPS will enter 

bypass mode or bypass mode can be set 
by front panel. Alarm is sounding every 
10 second.   

 

Standby mode 

UPS is powered off and no output supply 
power, but still can charge batteries. 

 

 
3-7. Faults Reference Code 

Fault event 

Fault code    Icon  Fault event 

Fault code    Icon 

Bus start fail 

01 

Inverter voltage Low 

13 

Bus over 

02 

Inverter output short 

14 

 

Bus under 

03 

Battery voltage too high  27 

 

Bus unbalance 

04 

Battery voltage too low 

28 

 

Inverter soft start fail 

11 

Over temperature 

41 

Inverter voltage high 

12 

Over load 

43 

 

 

Summary of Contents for NEWTECH PRO 1 KVA

Page 1: ...info tuncmatik com www tuncmatik com NEWTECH PRO 1 2 3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL ...

Page 2: ...s 3 2 Installation and setup 4 2 1 Rear panel view 4 2 2 Setup the UPS 6 3 Operations 8 3 1 Button operation 8 3 2 LCD Panel 8 3 3 Audible Alarm 10 3 4 LCD display wordings index 10 3 5 UPS Setting 10 3 6 Operating Mode Description 13 3 7 Faults Reference Code 13 3 8 Warning indicator 14 4 Troubleshooting 15 5 Storage and Maintenance 15 6 Specifications 16 ...

Page 3: ...ver them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the buil...

Page 4: ...s must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any...

Page 5: ... view NEWTECH PRO 1KVA NEWTECH PRO 2 KVA NEWTECH PRO 3 KVA TOWER TOWER TOWER NEWTECH PRO 1KVA 2KVA RACK NEWTECH PRO 3KVA RACK 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communication p...

Page 6: ...cal devices by setting shorter backup time for non critical devices For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm2 power cords Suggest using WG12 10 or 3 3mm2 5 3mm2 power cords for NEMA type c Upon completion of the wiring configuration please check whether the wires are secur...

Page 7: ...itial charge period Step 7 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software ...

Page 8: ...de UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to def...

Page 9: ...26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the Inverter circuit is work...

Page 10: ...breviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives There are 8 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program Param...

Page 11: ...uency setting Interface Setting Parameter 2 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Interface Setting Pa...

Page 12: ...0 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS Bypass low voltage point For 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac For 110 115 120 127 VAC models 85 115 setting the low voltage poi...

Page 13: ...ery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second Standby mode UPS is powered off and no output supply power but still...

Page 14: ...econd Battery is not connected Sounding every second Over Charge Sounding every second Site wiring fault Sounding every second EPO enable Sounding every second Fan Failure Sounding every second Over temperature Sounding every second Charger failure Sounding every second Out of bypass voltage range Sounding every second ...

Page 15: ...nd the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icon and is flashing on LCD display and alarm is sounding twice every second U...

Page 16: ...ce the battery The icon and the warning code flashing on LCD display and alarm is sounding every second Fan is locked or not working Check fans and notify dealer 5 Storage and Maintenance 5 1 Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your ...

Reviews: