21
17 programs available list for parameter 1:
Code Description
Bypass /
No Output mode
AC
mode
ECO
mode
CVCF
mode
Battery
mode
Battery
Test
01
Output voltage
Y*
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/disable
Y
06
Voltage range for ECO mode
Y
07
ECO mode frequency range setting
Y
08
Bypass mode setting
Y
Y
09
Battery backup time setting
Y
Y
Y
Y
Y
Y
10
Programmable output setting
Y
Y
Y
Y
Y
Y
11
Shutdown point for programmable
output
Y
Y
Y
Y
Y
Y
12
Reserved /Neutral Loss**
13
Battery voltage adjustment
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Inverter voltage adjustment
Y
Y
Y
16
Output voltage calibration
Y
Y
Y
17
Phase auto adapt enable/disable***
Y
*Y means that this program can be set in this mode.
**It is only available to operate when a loss of neutral line is detected. Otherwise, it will display “
” in
program setting menu.
***This function allows UPS input phase sequence more flexible. If it is enabled, UPS can adapt several kinds of
phase difference even it works like a single phase UPS. If it is disabled, UPS only can work under standard input
phase sequence among L1, L2, and L3. Please refer to program 17 below for more details about LCD setting.
01: Output voltage
Interface
Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208:
Presents output voltage is 208Vac
220:
Presents output voltage is 220Vac
230:
Presents output voltage is 230Vac
240:
Presents output voltage is 240Vac
02: Output frequency
Interface
Setting
60 Hz, CVCF mode
50 Hz, Normal mode
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three
options in parameter 2:
50.0Hz:
The output frequency is setting for 50.0Hz.
60.0Hz:
The output frequency is setting for 60.0Hz.
ATO:
If selected, output frequency will be decided according to
the latest normal utility frequency. If it is from 46Hz to 54Hz, the
output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the
output frequency will be 60.0Hz. ATO is default setting.