24
11: Shutdown point for programmable output
Interface
Setting
Parameter 2: 001.
Set shutdown time for programmable output.
Parameter 3: Shutdown time in minutes.
Setting range is from 0 to 300. When shutdown time arrives, the
programmable output terminal will be cut off. The default value is
30 minutes.
Parameter 2: 002
Set shutdown voltage for programmable output.
Parameter 3: Shutdown voltage in V.
Setting range is from 11.2 to 13.6. If the battery voltage is less
than the setting point, the programmable output will be cut off.
The default value is 11.2V.
12: Reserved/Neutral Line Loss
Interface
Setting
When input neutral line is correctly detected, “
” will be
displayed in parameter 2 and parameter 3.
When a loss of input Neutral line is detected, this program will
become “input Neutral line detecting” menu. It will display “
”
in parameter 2 and “
” in parameter 3. When it occurs, please
re-connect the input Neutral line well. Then, press the “Enter” key
to activate input Neutral line detecting. If it’s connected well and
correctly detected, it will show “
” in parameter 2 and
parameter 3 when entering the setting menu next time.
13: Battery voltage adjustment
Interface
Setting
Parameter 2:
Select “
Add
” or “
Sub
” function to adjust battery
voltage to real figure.
Parameter 3:
the voltage range is from 0V to 9.9V, the default
value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust charger
voltage
Parameter 3:
the voltage range is from 0V to 9.9V, the default
value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
*We strongly suggest to use the default value (0). Any
modification should be suitable to battery specifications.