7 SERVICE MANUAL FOR AMERICA
3 . R A T I N G
C O N D I T I O N S
Standard conditions in accordance with ANSI/AHAM RAC-1-2003, and UL 484.
Cooling:
Indoor: 80
o
FDB 67
o
F WB
Outdoor: 95
o
F DB 75
o
F WB
Heating:
Indoor: 70
o
F DB 60
o
F WB
Outdoor: 47
o
F DB 43
o
F WB
3 . 1 O p e r a t i n g
L i m i t s
Outdoor
Cooling
Upper limit (DB)
110
o
F
Lower limit (DB)
5
o
F
Heating
Upper limit (DB)
75
o
F
Lower limit (DB)
5
o
F
Voltage
2PH 198–264V/115V
3PH N/A
4 . O U T L I N E
D I M E N S I O N S
4.1 outdoor Unit: TAS-09EH/O