Assembly Object (04
hex
) (continued)
Assembly Object Class Attributes
The only supported Class attribute is 1 and it returns the revision number of the definition of the object . Because the RM-89
implements the CIP revision 2, this attribute will always return a value of “2” .
Assembly Instances
† See the Presetting the Position Value section on page 31 for an explanation of how to use the command byte .
‡ See the Program Parameters Instruction section on page 35 for information on the format of the parameter values .
DeviceNet Object (03
hex
)
Supported Services
The following table lists the services implemented by the RM-89 for the DeviceNet Object . The services that are implemented
only on the Class level (not on the Instance) should address Instance 0 .
Service
Code
Implemented
Service Name
Description of Service
Class
Instance
0E
hex
Yes
Yes
Get_Attribute_Single
Returns the contents of the specified attribute
10
hex
No
Yes
Set_Attribute_Single
Modifies an attribute value
Table B .3 DeviceNet Object Supported Services
Table B .2 Available Assembly Instances
Ser-
vice
Service
Code
Class
Instance
(decimal)
Attribute
Length
(bytes)
Data
Get
0E
hex
4
1
3
4
Position
Get
0E
hex
4
3
3
8
Position and Velocity
Get
0E
hex
4
104
3
8
Position and Time Stamp
Get
0E
hex
4
105
3
8
Position and Actual Sensor Reading
Get
0E
hex
4
101
3
5
32 bit Preset Value and 8 bit
command†
Set
10
hex
4
101
3
5
32 bit Preset Value and 8 bit
command†
Get
0E
hex
4
103
3
12
Programmable Parameter Values‡
Set
10
hex
4
103
3
12
Programmable Parameter Values‡