Exit programming mode: Press and hold the [M] button for at least 3 s 

until the display stops flashing.

Changing the temperature unit

 

Disconnect the sensor from the supply voltage.

 

Reconnect the sensor while pressing the [V/-] and [V/+] buttons

 

[°F] or [°C] appears on the display.

 

Change the temperature unit using the [V/+] button.

 

Confirm the selection using the [M] button.

 

The programmed values for t0 and t10 will be set to 0 °C/32 °F for 0 V and 

80 °C or 176 °F for 10 V after changing the temperature unit.

Changing the flow unit

 

Disconnect the sensor from the supply voltage.

 

Reconnect the sensor while pressing the [V/-] and [V/+] buttons

 

Enter the access code.

 

[GAL] or [L] appears on the display.

 

Select the flow unit using the [V/+] button.

 

Confirm the selection using the [M] button.

Resetting the device to the factory settings (see “Factory settings”)

 

Disconnect the sensor from the supply voltage.

 

Reconnect the sensor while pressing the [M] button.

 

[rES] appears on the display.

 

Enter the access code.

 

To reset the device, press the [M] button.

Maintenance

Operating the device in contaminated or chalky water causes deposits that 

can distort measurements.

 

Clean the part of the sensor through which the medium flows. During 

cleaning, ensure that the metallic surface of the sensor is not damaged.

Repair

The device must not be repaired by the user. The device must be decom-

missioned if it is faulty. Observe our return acceptance conditions when 

returning the device to Turck.

Disposal

The devices must be disposed of correctly and must not be included 

in normal household garbage.

EN

Quick-Start Guide

Operation

The device has three buttons on the front that can be used to activate func-

tions and configure settings. All values are shown in the display.

Button

Function in normal mode

Function in programming mode

V/-

Displays the current value for 

the flow rate in V

Reduces the displayed value

V/+

Displays the current value for 

the temperature in V

Increases the displayed value

M

Displays the currently measured 

temperature or the current flow 

rate for 3 s

Selects functions and  

parameters

Changing the displayed value

 

Press the [M] button as per the table below: 

Press [M] Displayed function

Possible display values

1x

Current temperature

-10…+90

2x

Initial temperature value 0 V (t0) 14…162 °F/-9.9…+74.0 °C

3x

Final temperature value 10 V (t10) 46…194 °F/6.1…90.0 °C

4x

Time interval for mean value 

generation (nfi)

2…16

5x

Fluid (FLU)

GLY, di, 110, 135

 

The selected value is shown on the display for approximately 3 s.

Setting

 

Start programming mode: Press and hold the [V/-] and [V/+] buttons at 

the same time for at least 3 s until the display starts to flash.

 

Enter the access code (factory setting: 0).

 

Select the value to be set: Press the [M]

 

button as per the table below:

Press

 

[M] Configurable function

Possible display values

1x

Enter the access code (Cod)

0…255

2x

Initial temperature value 0 V in 

°F (t0)

14…162 °F

3x

Final temperature value 10 V in 

°F (t10)

46…194 °F

4x

Time interval for mean value 

generation (nfi) 

2…16

5x

Fluid (FLU)

GLY: glycol 0…70 %

di: deionized water

110: HT110

135: HT135

6x

Reference function ± 25 % (CAL)

7x

Configure the display: tempera-

ture only, flow rate only, flow 

rate and temperature alter-

nately (diS)

°F…GAL…°FG

8x

Change the access code (COD) 0…255

Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | more@turck.com | www.turck.com

© Hans Turck GmbH & Co. KG | 100017718 2020-03 EN 

FTCI-3/4D15A4P-2LUX-H1141

Technical Data

Technical data

FTCI-3/4D15A4P-2LUX-H1141

Ident-No.

6878041

Supply voltage

24 V DC ± 10% (PIN1: BN +, PIN3: BU -)

Current consumption

100 mA

Ambient temperature

32…140 °F

Output 1

Flow – analog 0…10 V (PIN 4: BK)

Output 2

Temperature – analog 0…10 V (PIN 2: WH)

Load

50…500 Ω

Medium temperature

14…194 °F

Detection range flow

Water

Water/monoethylenglycol 0…70 %

1…12 gpm

1…12 gpm

Display range

0.8…14.4 gpm

Detection range temperature

14…194 °F

Accuracy temperature

± 5 °F (68…158 °F: ± 3.0 °F) (Flow rate > 

3 gpm)

Adjustment range temperature

4 mA: 14…162 °F
20 mA: 46…194 °F
t20 mA – t4 mA ≥ 32 °F

Reaction time

2…8 s

Material sensor

AISI 316 Ti / FKM

Material housing

PBT

Protection

IP 65

Compressive strength

20 bar

Factory setting code

0

Factory Settings

Unit flow

gpm

Unit temperature

°F

t0

32 °F

t10 

176 °F

nFi

8

Medium

Water

Display

Flow only (gal)