Operating
Measurement value representation of analog modules
184
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
-1…1 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.05185 × 10
-5
) V
> 1.0100 V
"Upper limit value exceeded” ON
32767
7FFF
< 1.0050 V
"Upper limit value exceeded" OFF
32767
7FFF
1.0000 V
Nominal range
32767
7FFF
0.999 V
32766
7FFE
0.996 V
32736
7FE0
0 V
16
0010
0 V
1
0001
0 V
0
0000
0 V
-1
FFFF
0 V
-16
FFF0
-0.909 V
-32752
8010
-0.999 V
-32767
8001
-1.000 V
-32768
8000
> -1.0050 V
"Lower limit value underrun" OFF
-32768
8000
< -1.0100 V
"Lower limit value underrun" ON
-32768
8000
-500…500 mV
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 1.5259 × 10
-2
) mV
> 505.0 mV
"Upper limit value exceeded” ON
32767
7FFF
< 502.5 mV
"Upper limit value exceeded" OFF
32767
7FFF
500.000 mV
Nominal range
32767
7FFF
499.95 mV
32766
7FFE
499.527 mV
32736
7FE0
244.244 mV
16
0010
0.015 mV
1
0001
0 mV
0
0000
-0.015 mV
-1
FFFF
-244.244 mV
-16
FFF0
-499.771 mV
-32752
8010
-499.999 mV
-32767
8001
-500.000 mV
-32768
8000
> -502.5 mV
"Lower limit value underrun" OFF
-32768
8000
< -505.0 mV
"Lower limit value underrun" ON
-32768
8000