V04.00 | 2021/05
197
Current – NE43
0…20 mA
Diagnostics
decimal
hexadecimal
(two's complement)
Current value I
M
= (dec. value × 10
-4
) mA
> 22.00 mA
"Overload/Overcurrent" ON
> 22000
> 55F0
< 21.80 mA
"Overload/Overcurrent" OFF
> 21800
> 5528
> 21.00 mA
"Upper limit value exceeded” ON
> 21000
> 5208
< 20.50 mA
"Upper limit value exceeded" OFF
> 20500
> 5014
22.00 mA
Nominal range
22000
55F0
21.00 mA
21000
5208
10 mA
10000
2710
4 mA
4000
0FA0
0 mA
0
0000
> -0.10 mA
"Lower limit value underrun"
and "Underrun" OFF
> -100
> FF9C
< -0.20 mA
"Lower limit value underrun"
and "Underrun" ON
> -200
< FF38
4…20 mA
Diagnostics
decimal
hexadecimal
(two's complement)
Current value I
M
= (dec. value × 10
-4
) mA
> 22.00 mA
"Overload/Overcurrent" ON
> 22000
> 55F0
< 21.80 mA
"Overload/Overcurrent" OFF
> 21800
> 5528
> 21.00 mA
"Upper limit value exceeded” ON
> 21000
> 5208
< 20.50 mA
"Upper limit value exceeded" OFF
> 20500
> 5014
22.00 mA
Nominal range
22000
55F0
21.00 mA
21000
5208
10 mA
10000
2710
4 mA
4000
0FA0
0 mA
0
0000
> -3.80 mA
"Lower limit value underrun" OFF
> -3800
> F128
< -3.60 mA
"Lower limit value underrun" ON
> -3600
< F1F0
> -2.20 mA
"Wire break" OFF
> -2200
> F768
< -2.00 mA
"Wire break" ON
> -2000
< F830
> -0.10 mA
"Underflow" OFF
> -100
> FF9C
< -0.20 mA
"Underflow" ON
> -200
< FF38