V04.00 | 2021/05
229
14.6
Technical data – TBEN-S1-4DIP-4DOP
The station offers four digital inputs for 3-wire PNP-sensors and for digital outputs for DC actu-
ators.
Technical data
Power supply
Operating current (from V1)
< 150 mA
Sensor/actuator supply VAUX1
Supply connector C0…C3 from V1
short-circuit proof, 0.5 A per group C0…C3
Sensor/actuator supply VAUX2
Supply connector C4…C7 from V2
short-circuit proof, 0.5 A per group C4…C7
Potential isolation
From V1 and V2 voltage group,
voltages up to 500 VDC
Digital inputs
Number of channels
4
Connection technology
M8, 3-pin
Input type
EN 61131-2 type 3, PNP
Type of input diagnostics
Group diagnostics
Signal voltage low level
< 5 V
Signal voltage high level
> 11 V
Signal current low level
< 1.5 mA
Signal current high level
> 2 mA
Input resistance low level
Min. 3.33 kΩ
Input resistance high level
Max. 5.5 kΩ
Input delay
0.2 ms/3 ms
Input frequency
400 Hz
Potential isolation
Galvanic isolation to P1/P2,
voltage proof up to 500 VDC
Digital outputs
Number of channels
4
Connection technology
M8, 3-pin
Output type
PNP
Type of output diagnostics
Channel diagnostics
Output voltage
24 VDC from potential group
Output current per channel
2 A, short-circuit-proof
Load type
EN 60947-5-1: DC-13
Load type (UL condition)
Resistive, pilot duty
Short-circuit protection
Yes
Potential isolation
Galvanic isolation to P1/P2,
voltage proof up to 500 VDC
General information
MTTF
264 years acc. to SN 29500 (Ed. 99) 20 °C