[12]
G: Alarm Condition Monitoring Outputs
- This is optional, and is
not necessary for all applications. If you would like to monitor all the outputs, a 22awg/14
conductor is required.
H: Remote Lane Control -
Pushbutton, or hard wired Remote Lane Control Inputs
-
A 22awg/14 conductor is required to run to all of the pedestals except the last pedestal in
order to operate the pushbutton or hardwired RLC with full functionality.
Note: To activate any mode or feature (i.e. Free Exit) simply provide a jumper from that point to ground.
22/14 from RLC-PB to PIO Board,
Connector J16
Listed From bottom to top
Point #
Description
16
Visitor Enter
15
Visitor Exit
14
Reset Lane
13
Optical Mode
12 Enter Only
11
Exit Only
10
Free Exit
9
Reset Barrier
8
Security Disable
7
Close Lane
6
No Acknowledgement
5
Option 2
4
Alarm Lamp Output
3
Ground (Common)
2
24vdc
1
Ground
Connector J14 - Relay Outputs
1&2 = ENTER INTRUSION
3&4 = ENTER TAILGATE
5&6 = EXIT INTRUSION
7&8 = EXIT TAILGATE
9&10 = VALID ENTER
11&12 = VALID EXIT
13&14 = CRAWL
15&16 = DISABLE ENTER READER
17&18 = DISABLE EXIT READER