10
The 825 meter is designed to be recalibrated with water for
safe handling. Over time, the chamber inside the meter will
wear. Recalibrating the meter with clean water will insure that
Table #1 is most accurate.
You will need a container of known volume, at least 5 gallons
or larger. Do not exceed a 60 gallon container.
1.
1.
1.
1.
1. Press the 2 & 4 buttons at the same time
and hold for 3 seconds.
The display will read the version of the software loaded in the
meter (example: "7r1.02").
2.
2.
2.
2.
2. Press button 3 to enter calibration mode.
The unit of measure will be displayed.
3.
3.
3.
3.
3. Press button 3 .
The display will read "FILL".
4.
4.
4.
4.
4. Now dispense water into your container. "FILL" will flash on
the display.
5.
5.
5.
5.
5. After dispensing, press the ON button.
The left digit of the display will blink.
6.
6.
6.
6.
6. Press the 4 button to increment the digit to the amount
of fluid dispensed (example: 05.00).
Press the ON button to move to the right.
If you make a mistake, press button 2 to start back at the
left- most digit.
7.
7.
7.
7.
7. After number is loaded, press the ON button again
to accept.
88888. Display now shows .
Since you are calibrating with water, accept this by press
ing the ON button again. If calibrating with a fluid other
than water, see Appendix-C. Display will again
show "7r1.02".
Note: If the value entered is out of an acceptable range, the
display will read "Err0" and the meter will revert to the
previous settings. See Troubleshooting Guide for more
information.
99999. Press 2 to get back to the normal operating mode.
7
r 1. 0 2
GAL
QT
Move to Right
Increment No.
F I L L
0 0.0 0
CAL
4
APPENDIX-B Water Calibration
7
r 1. 0 2
CAL
4