background image

ACM 400 S motor control unit 

 

 

13 / 24 

r)  Universal output 

[X12]

 

 
This  universal  output  consists  of  a 

floating  changeover  contact

,  which  can  be 

started with different functions, for example... 

  for  the 

self-test 

of  the  transmitter  side  of  photoelectric  barriers:  During  the  self-

test (page 17) the changeover contact briefly picks up and can therefore interrupt 
a  power  supply  passed  via  the 

break  contact  element

 

(terminals  16  /  18) 

– 

which  must  be  recognised  as  a  command  at  the  photoelectric  barrier  input  after 
max 0.5s. 

  for  connecting a 

traffic  signal  light

: To do this, connect the “red” signal light to 

the  break  content  element  and  “green”  to  the  make  contact  element.  The 
changeover  contact  does  not  pick  up  until  the  limit  position  "Open",  along  the 
gate’s path and in the "Closed" limit position the signal light remains "red". 

  for special functions to be switched on 

by radio button

, e.g. bell, time switch or 

pulse  for  garage  gates.  The  changeover  contact  picks  up  if  a  radio  signal  is 
correctly received on channel 4. 

 

Menu “F” value 

Universal output terminals 16…18 

00

 

Self-test function 

01

 

Traffic light function 

02

 

Radio button (channel 4) 

 
 

s)  Radio receiver (optional) 

[X4]

 

 
If  an  optional  radio  receiver  is  installed,  as  described  in  the  radio  receiver 
instructions, the following functions are available: 
 

Channel  

Function 

1

 

“Pulse“ (page 10f) 

2

 

“Open“  (see table) 

3

 

“Closed“   (see table) 

4

 

Partial opening function (page 11), or Universal output (menu 

“F” 

= 02) 

 

Radio command 
causes 

Menu “C” value 

While opening 

While closing 

“Open“ (channel 2) 

00

 

Stop 

Stop 

01

 

closes 

02

 

Stop 

Stop 

03

 

closes 

“Closed“  (channel 3) 

00

 

Stop 

Stop 

01

 

Stop 

Stop 

02

 

opens 

03

 

opens 

 
 

Summary of Contents for ACM 400 S

Page 1: ...302_ACM400S_EN doc 1 24 ACM 400 S 1 motor 230V 400 gate control unit Assembly installation connection and programming instructions for the fitter Please keep these instructions in a safe place so you...

Page 2: ...r sensors X7 11 m Method of connection for self test 11 n Speed sensor X7 11 o Photoelectric barrier X7 11 p Closing edge safety device X7 11 q Light outputs X10 12 r Universal output X12 13 s Radio r...

Page 3: ...ta based on software status ACM400S V1 4 Parameter Symbol Limit values Units Test conditions Min Typical Max Power supply System voltage 1 230V UNetz1 205 230 255 VAC At terminals 5 8 System voltage 3...

Page 4: ...put resistance RZUin 625 Pull Up from 5V Closed Pulse duration debounce tZU 50 ms Stop not actuated open UStop 0 4 0 5 0 V An terminals 29 0V Stop actuated closed UStop 1 0 0 1 0 V An terminals 29 0V...

Page 5: ...s The end product manufacturer is thus responsible for compliance and declaration of CE conformity The control unit complies with the requirements in DIN EN 60204 EN 13241 1 EN 61000 6 2 EN60335 1 EN...

Page 6: ...ating moisture X13 The weight of the control unit is approx 1 7 kg Please take this into account when choosing the type of fixing Install the control unit housing professionally at the suitable instal...

Page 7: ...to terminals L1 3 N PE c 400V motor 3 X14 The load tap of the motor control unit and 3 phase operation is designed for a max motor output of 2000W 400V However a max operating time of 25 must not be...

Page 8: ...0 Stop is a purely function input without safety function Gate status Open pressed Closed pressed Stop pressed standing in limit position Open closes standing in limit position Closed opens standing i...

Page 9: ...Textmarke nicht definiert is also possible via the membrane keyboard i Universal input X8 1 With this you can realise both optional partial opening mode and Automatic closing Partial opening mode ena...

Page 10: ...keep open time standing in partial opening position Automatically closes after expiry of the keep open time keep Open button pressed Stays open keep open time starts running again Closed button presse...

Page 11: ...et via menu 0 X7 1 Connect the signal output to terminals 19 20 Gate status Reaction Standing running Menu 0 value 00 no sensor connected 01 Type Castalia connected If signal cannot be measured 0 5s a...

Page 12: ...Stop 14 14 30 closes Release 15 15 31 closes opens Release if an obstruction is detected the gate moves a short distance in the opposite direction released Release time in 0 25s steps Menu B value 00...

Page 13: ...the limit position Open along the gate s path and in the Closed limit position the signal light remains red for special functions to be switched on by radio button e g bell time switch or pulse for ga...

Page 14: ...ive inputs outputs X6 1 At terminals 23 39 lit LEDs mean that the respective inputs have been triggered or are not closed off X6 2 At terminals 40 42 lit LEDs mean that the respective limit switch has...

Page 15: ...t switch within 2s of starting Restart motor If error remains Gate won t move Check mechanics motor transmission emergency unlocking gate frozen Gate moves Check limit switch contact wiring or speed s...

Page 16: ...u item appears in the display You can now use the keys to change the value as described on pages 8 16 The value is immediately adopted as soon as you set it d Reset You can reset the values to the fac...

Page 17: ...control unit constantly performs various self tests If an error occurs the control unit is locked and an error message is displayed see table on page 15 Faulty self tests are automatically repeated a...

Page 18: ...mergency operation In order to enable controlled movement of the gate when safety equipment closing edge safety device photoelectric barrier is continuously actuated e g in case of a defect in a safet...

Page 19: ...pen Closed Pulse and Partial opening functions or the universal output a radio receiver can be installed in the Radio slot see page 13 X4 This is described in greater detail in the installation instru...

Page 20: ...Stop Stop 22 OSE Stop Release 23 OSE Stop Reversing 24 OSE Release No effect 25 OSE Release Stop 26 OSE Release Release 27 OSE Release Reversing 28 OSE Reversing No effect 29 OSE Reversing Stop 30 OS...

Page 21: ...g Stop while closing panic function 02 RADIO OPEN Stop while opening Stop while closing panic function RADIO CLOSED Reversing while opening no effect while closing 03 RADIO OPEN No effect while openin...

Page 22: ...ACM 400 S motor control unit 22 24 13 Figures Diagrams X1 X5 X7 X8 X9 X4 X3 X2 X6...

Page 23: ...ACM 400 S motor control unit 23 24 X10 X12 X13 X14 X17 X15 X18 X16 X19 X11...

Page 24: ...ACM 400 S motor control unit 24 24 14 Block CIRCUIT DIAGRAM...

Reviews: