ACM 400 S motor control unit
13 / 24
r) Universal output
[X12]
This universal output consists of a
floating changeover contact
, which can be
started with different functions, for example...
for the
self-test
of the transmitter side of photoelectric barriers: During the self-
test (page 17) the changeover contact briefly picks up and can therefore interrupt
a power supply passed via the
break contact element
(terminals 16 / 18)
–
which must be recognised as a command at the photoelectric barrier input after
max 0.5s.
for connecting a
traffic signal light
: To do this, connect the “red” signal light to
the break content element and “green” to the make contact element. The
changeover contact does not pick up until the limit position "Open", along the
gate’s path and in the "Closed" limit position the signal light remains "red".
for special functions to be switched on
by radio button
, e.g. bell, time switch or
pulse for garage gates. The changeover contact picks up if a radio signal is
correctly received on channel 4.
Menu “F” value
Universal output terminals 16…18
00
Self-test function
01
Traffic light function
02
Radio button (channel 4)
s) Radio receiver (optional)
[X4]
If an optional radio receiver is installed, as described in the radio receiver
instructions, the following functions are available:
Channel
Function
1
“Pulse“ (page 10f)
2
“Open“ (see table)
3
“Closed“ (see table)
4
Partial opening function (page 11), or Universal output (menu
“F”
= 02)
Radio command
causes
Menu “C” value
While opening
While closing
“Open“ (channel 2)
00
Stop
Stop
01
-
closes
02
Stop
Stop
03
-
closes
“Closed“ (channel 3)
00
Stop
Stop
01
Stop
Stop
02
opens
-
03
opens
-