ACM 400 S motor control unit

 

14 / 24

 

7) Putting into Service

 [X2]

 

 
If the control unit has been installed and connected as described, it can now be put 
into service: 

 

non-connected inputs

 are closed, as far as necessary, 

e.g. at the inputs for ... 

  Emergency stop (page 

Fehler! Textmarke nicht definiert.

  Photoelectric barrier (page 

Fehler! Textmarke nicht definiert.

  Closing edge safety device (page 

Fehler! Textmarke nicht definiert.

  Ensure safety, regarding the remaining part of the 

whole system

, in particular ... 

  ensure  that  when  the  motor  is  started  up  nobody  can  be  injured  and  the 

system cannot be damaged. 

It makes sense, when switching the gate on for the first time, for the gate to be in the 

middle

  of  the  gate  path,  to  allow  sufficient  reaction  time  if  unexpected  movements 

occur. 
If you now switch on the system voltage, a complete 

self-test 

(see page 17) is now 

carried out. 
[X2.1]  The 

display

  first  displays 

"88"

  and  then 

"CH"

  as  an  indication  that  the  self-

test is running. 
 
 

a)  The LEDs on the printed circuit board 

signal the switched condition of the respective 

inputs / outputs:

 

 
[X6.1]  At  terminals 

23...39

,  lit  LEDs  mean  that  the  respective 

inputs

  have  been 

triggered or are not closed off. 
[X6.2]  At  terminals 

40...42

,  lit  LEDs  mean  that  the  respective 

limit  switch  has 

triggered

, i.e. the gate is in this limit position. 

[X2.5] The lit LEDs 

under the display

 mean that the outputs for 

light and warning 

light 

conduct voltage at 

terminals 9...11

[X2.1]  The 

left-hand  display  point 

lights  up  if  a  signal  from  the 

speed  sensor

  is 

received at 

terminals 19...20

[X2.1] The 

right-hand display point 

lights up, if 

automatic closing

 is activated. 

 
 

b) The LEDs on the membrane keyboard 

[X5]

 

 
signal the 

gate status

 and indicate error statuses: 

[X5.1] The 

"Running"

 LED lights up... 

  continuously during normal operation 
  flashes if errors occur according to the "error messages" table. 

[X5.2] The LED 

"A"

 (gate) lights up... 

  continuously, if the gate is in the limit position "Open", 
  does not (= off), if the gate is in the limit position "Closed",  
 

flashes slowly (0.5Hz), if the gate is stopped along the gate’s path,  

  flashes quickly (4 Hz), if the gate is moving open or closed. 

[X5.3] The LED 

"B"

 (radio) lights up if a valid 

radio command

 has been analysed. 

[X5.4] The LED 

"S"

 lights up if an error has been detected (e.g. a sensor triggered or 

Emergency Stop or undervoltage). 

Summary of Contents for ACM 400 S

Page 1: ...302_ACM400S_EN doc 1 24 ACM 400 S 1 motor 230V 400 gate control unit Assembly installation connection and programming instructions for the fitter Please keep these instructions in a safe place so you...

Page 2: ...r sensors X7 11 m Method of connection for self test 11 n Speed sensor X7 11 o Photoelectric barrier X7 11 p Closing edge safety device X7 11 q Light outputs X10 12 r Universal output X12 13 s Radio r...

Page 3: ...ta based on software status ACM400S V1 4 Parameter Symbol Limit values Units Test conditions Min Typical Max Power supply System voltage 1 230V UNetz1 205 230 255 VAC At terminals 5 8 System voltage 3...

Page 4: ...put resistance RZUin 625 Pull Up from 5V Closed Pulse duration debounce tZU 50 ms Stop not actuated open UStop 0 4 0 5 0 V An terminals 29 0V Stop actuated closed UStop 1 0 0 1 0 V An terminals 29 0V...

Page 5: ...s The end product manufacturer is thus responsible for compliance and declaration of CE conformity The control unit complies with the requirements in DIN EN 60204 EN 13241 1 EN 61000 6 2 EN60335 1 EN...

Page 6: ...ating moisture X13 The weight of the control unit is approx 1 7 kg Please take this into account when choosing the type of fixing Install the control unit housing professionally at the suitable instal...

Page 7: ...to terminals L1 3 N PE c 400V motor 3 X14 The load tap of the motor control unit and 3 phase operation is designed for a max motor output of 2000W 400V However a max operating time of 25 must not be...

Page 8: ...0 Stop is a purely function input without safety function Gate status Open pressed Closed pressed Stop pressed standing in limit position Open closes standing in limit position Closed opens standing i...

Page 9: ...Textmarke nicht definiert is also possible via the membrane keyboard i Universal input X8 1 With this you can realise both optional partial opening mode and Automatic closing Partial opening mode ena...

Page 10: ...keep open time standing in partial opening position Automatically closes after expiry of the keep open time keep Open button pressed Stays open keep open time starts running again Closed button presse...

Page 11: ...et via menu 0 X7 1 Connect the signal output to terminals 19 20 Gate status Reaction Standing running Menu 0 value 00 no sensor connected 01 Type Castalia connected If signal cannot be measured 0 5s a...

Page 12: ...Stop 14 14 30 closes Release 15 15 31 closes opens Release if an obstruction is detected the gate moves a short distance in the opposite direction released Release time in 0 25s steps Menu B value 00...

Page 13: ...the limit position Open along the gate s path and in the Closed limit position the signal light remains red for special functions to be switched on by radio button e g bell time switch or pulse for ga...

Page 14: ...ive inputs outputs X6 1 At terminals 23 39 lit LEDs mean that the respective inputs have been triggered or are not closed off X6 2 At terminals 40 42 lit LEDs mean that the respective limit switch has...

Page 15: ...t switch within 2s of starting Restart motor If error remains Gate won t move Check mechanics motor transmission emergency unlocking gate frozen Gate moves Check limit switch contact wiring or speed s...

Page 16: ...u item appears in the display You can now use the keys to change the value as described on pages 8 16 The value is immediately adopted as soon as you set it d Reset You can reset the values to the fac...

Page 17: ...control unit constantly performs various self tests If an error occurs the control unit is locked and an error message is displayed see table on page 15 Faulty self tests are automatically repeated a...

Page 18: ...mergency operation In order to enable controlled movement of the gate when safety equipment closing edge safety device photoelectric barrier is continuously actuated e g in case of a defect in a safet...

Page 19: ...pen Closed Pulse and Partial opening functions or the universal output a radio receiver can be installed in the Radio slot see page 13 X4 This is described in greater detail in the installation instru...

Page 20: ...Stop Stop 22 OSE Stop Release 23 OSE Stop Reversing 24 OSE Release No effect 25 OSE Release Stop 26 OSE Release Release 27 OSE Release Reversing 28 OSE Reversing No effect 29 OSE Reversing Stop 30 OS...

Page 21: ...g Stop while closing panic function 02 RADIO OPEN Stop while opening Stop while closing panic function RADIO CLOSED Reversing while opening no effect while closing 03 RADIO OPEN No effect while openin...

Page 22: ...ACM 400 S motor control unit 22 24 13 Figures Diagrams X1 X5 X7 X8 X9 X4 X3 X2 X6...

Page 23: ...ACM 400 S motor control unit 23 24 X10 X12 X13 X14 X17 X15 X18 X16 X19 X11...

Page 24: ...ACM 400 S motor control unit 24 24 14 Block CIRCUIT DIAGRAM...

Reviews: