ACM 400 S motor control unit
3 / 24
1) Safety Characteristics
Self-monitoring inputs for photoelectric barrier and closing edge safety device
Motor monitoring through speed sensor
Path monitoring through photoelectric barrier and up to four safety strips
Self-monitoring functions of the control unit: Watchdog, RAM/ROM and
EEPROM, undervoltage
All-pole motor cut-out
Motor running time limit
2) Intended Purpose
This
motor control unit
is intended for 230V and 400V drive units
for 1-motor gates (e.g. rotary, sliding, tiling and swing gates as garage or
courtyard gate systems)
in industrial, residential, business and commercial areas and for small
businesses,
according to the specifications in these instructions.
These
instructions
are intended for the fitter and further processing industry,
however are not for issuing to the owner/operator of the gate system.
The end product manufacturer is responsible for preparing instructions suitable for
the owner/operator of the gate system.
3) Technical Specifications
Safe operation of the control unit with all its functions is only possible if all the named
values are adhered to! Data based on software status ACM400S V1.4
Parameter
Symbol
Limit values
Units
Test conditions
Min.
Typical
Max.
Power supply
System voltage 1~ 230V
U
Netz1
205
230
255
V
AC
At terminals 5 / 8
System voltage 3~ 400V
U
Netz3
360
400
440
V
AC
An terminals 5 / 6 / 7
Total Maximum Power
1500
VA
1~230V
Total Maximum Power
3200
VA
3~400V
System frequency
f
Netz
48
50
52
Hz
Internal logic voltage
U
V
4.8
5.0
5.2
V
Power input
P
Prim
8
10
VA
Primary, without plug-in card, at rest/idle mode
Starting time system voltage / 1.
Start
t
Start
2.5
3.5
s
@ U
Netz
= 230V
AC
Inputs
Speed sensor Low-level
U
DSLow
0.7
4.2
V
An terminal 19/20, depending on setting menu 00
Speed sensor High-level
U
DSHigh
1.3
4.4
V
An terminal 19/20, depending on setting menu 00
Speed sensor frequency
f
DS
10
500
Hz
ES Open / Closed not actuated
(closed)
U
ESclosed
9.0
V
terminal 40 / 0V, terminal 42 / 0V
ES Open / Closed actuated
(open)
U
ESopen
1.0
V
terminal 40 / 0V, terminal 42 / 0V
ES Open / Closed Strom (closed)
I
ES
28
40
mA
Via terminals 40/41, 42/41
Emergency stop not actuated
(closed)
U
NOTclosed
0.0
0.5
V
Via terminals 38/39
Emergency stop actuated (open)
U
NOTopen
1.0
V
terminals 39 / 0V
Emergency stop Strom (closed)
I
NOT
33
45
mA
Via terminals 38/39
Photoelectric barrier not actuated
(closed)
U
Lsclosed
0.0
0.5
V
terminals 31 / 0V
Photoelectric
barrier
actuated
(open)
U
Lsopen
4.0
V
terminals 31 / 0V