SELF TESTING MAINTAINED EMERGENCY LUMINARY

GENERAL

o

These  luminaires  are  used  indoors 

(

ta  40 C

)

  where  emergency 

light is needed.
Each luminaire must be permanently connected to mains power 
supply

.

  In  normal  operation  the  illumination  LEDs  are  lit  as  well 

as  the  green  indicating  charge  LEDs  when  the  battery  is 
charging. In case of a mains power supply failure, the luminaire  
enters in emergency mode and will light automatically. When the 
mains  power  supply  is  restored  the  device  turns  to  normal 
operation.

INSTALLATION

To install the luminaire follow the installation instructions on page 
3.

Battery Charging

The  battery  charging  procedure  is  controlled  by  the  processor, 
thus maintaining  its best possible  preservation, as it extends its 
duration.

Battery Cut-off

The  luminaire  enters  this  mode  when  the  mains  power  supply 
fails

 

and battery has lost all its energy

During this operation the 

luminaire  enters  the  idle  state

 

and  battery  consumption  is 

negligible, in order to be protected from deep discharge.

Manual

 

Operational 

Test

This test can be done by pressing the test 
button. The light source and the emergency circuit of the device 
are monitored for 3 sec. The manual test can be conducted only 
if the mains power supply and the battery are connected. During 
this test period all indication LEDs are OFF. 

Automatic Operational Test

This  test  includes  all  the  operations  of  the  manual  test  and  is 
conducted  automatically  every  15  days.  In  order  to  be 
performed,  the  mains  power  supply  and  the  battery  should  be 
connected. 

Automatic Autonomy Test

The  Automatic  Autonomy  Test  measures  the  device’s  back  up 
operation  and  emergency  duration.  This  test  is  conducted 

automatically  every  6  months

In  order  to  be  performed,  the 

mains  power  supply  and  the  battery  should  be  connected  and 
fully  charged

If  the  battery  is  not  fully  charged

the  test  is 

postponed

 

until  the  battery  is  completely  charged.  If  during  this 

test, the autonomy is less than nominal, the battery fault led turns 
on continuously and the battery must be replaced. 

Emergency Operation

The  autonomy  duration  of  battery  during  emergency  mode  is  at 
least  90  or  180  minutes,  depending  on  the  model.  During 
emergency mode, a light source test is also performed.

Resetting Errors

Push the Test button for more than 10 seconds, to delete all the 
indicated  LED  errors.  Then    the  device  enters  regular

 

operation 

mode.

Indication LED status (with connected mains power supply).

Charge

 (Green LED)

 

Blink: 

Battery is charging.

On:

 

Good charge condition.

Οff:

 

No battery 

(

No charging current 

or disconnected battery

).

Fault (Red LED)

 

Οn

 

:

 

Faulty  LED  strip  (must  be  replaced)  or  emergency  circuit 

(must be checked by an authorized personnel).

Blink

 (

With Charge LED ON):

 Autonomy or low battery problem 

(the battery must be replaced).

Οff:

 

LED strip and battery ok.

Connection to module

This luminaire can be connected to any of the following modules: 
Remote  module,  address  module,  wireless  module  and  fault 
relay module. If you connect it to a module that supports inhibit 
or  rest  mode,  you  should  know  that  these  commands  can  be 
cancelled  only  during  normal  mode  (ie.  not  in  emergency).  For 
installation refer to step 5 of the istallation procedure in page 3.
Also  refer  to  the  user’s  manual  of  each  module  for  additional 
information.

GR-2110/ST

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

220-240V AC/50-60Hz

3 h

1.5 h

24 h

16 h

IP30

3.6V/1.5Ah

3.6V/600mAh

3.3W / 3.6VA

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

5 to 40  C

o

up to  95% 

ABS/PC,PC

544gr.

463gr.

2

92

 

x 111 x 54 mm

  100lm / 100lm

22

m

  12 White LEDs

TECHNICAL CHARACTERISTICS

 (

for LED MODULE Specs. see page 2)

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY

  (

Ni-Cd

)

 

CHARGING TIME

INDICATIONS 

CONTROLS

MINIMUM AUTONOMY DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

ILLUMINATION

 

(230V AC

 

/ emergency) 

VEWING DISTANCE

ILLUMINATION SOURCE 

Battery and charge Fault indication LEDs

TEST button

3 years 

(1 

year for the battery

)

GR-2100/ST/M

GR-2110/ST/M

Reviews: