Rebar Scanner A60+
35
Figure 5-3
Step 5 Detect covering layer thickness and rebar diameter
Detect covering layer thickness under the condition of known rebar
diameter:
Select the function of Thickness Test of instrument and
set
No. and rebar diameter properly.
Carry out scanning in the middle
position of two pieces of stirrups (lower rebar) along the direction that
is vertical to main rebar (top rebar) to determine the covering layer
thickness of detected main rebar (top rebar). Carry out scanning in the
middle position of two pieces of stirrups (top rebar) along the
direction that is vertical to stirrups (lower rebar) to determine the
covering layer thickness of detected stirrups (lower rebar). Pay
attention to setting the status of corresponding grid pattern rebar.
Detect covering layer thickness and rebar diameter under the
condition of unknown rebar diameter:
Select the function of Diameter
Test of instrument and
set No properly.
Carry out scanning in the
middle position of two pieces of stirrups (lower rebar) along the
direction that is vertical to main rebar (top rebar) by means of probe in
parallel to the rebar to determine the accurate position of detected