Twin Disc, Incorporated
Troubleshooting
Power Transmission System Operator’s Manual #1020510
TRAN SYS FAULT Message -- OUT1 SPD Log Code
This fault message will be displayed if the control recognizes an open or short
in the transmission output speed sensor circuit. The display message will not
be cleared until the fault is corrected and the controller is repowered by cycling
the key switch. The proper impedance of the sensor when checked by using an
ohmmeter should be 1000 to 1300 ohms. This can be checked across terminals
J3A1
and
J3B1
at the plug when it is removed from the control. There should
be no circuit between either of these terminals and the chassis ground which is
J4X3
.
If the measured impedance is not proper at these points, the cable must
be disconnected at the sensor, and at the transmission junction to determine
the location of the fault.
Note:
If both the transmission input speed sensor and the
transmission output speed sensor fail simultaneously
while the oil well fracturing rig is pumping, the following
will happen:
A.
The torque converter lockup clutch range valve will be de-energized.
B.
The present transmission range will be held until the operator selects
neutral.
C.
Warm-up will not be allowed.
The above actions will be maintained until the fault is corrected and the control
is repowered by cycling the key switch.
Summary of Contents for TA-90-8501
Page 3: ...Document Number 1020510 Revison 1 May 2002 Power Shift Transmission System Operator s Manual ...
Page 4: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......