VIGILANT F08 Installation & Programming Manual
Programming
PROGRAMMING FEATURES (CONTINUED)
FUNCTION 4; ZONE & ANCILLARY RELAY SUPERVISION - ENABLED / DISABLED;
AUXILIARY
ZONE
OUTPUT
OPERATION
MODE
This programming function enables the programmer to select which zone inputs are enabled
and also select whether or not the Ancillary Relay Output is Supervised. Disabled zones do
not require EOL units and are inhibited from any zone or system tests.
This function is also used to select whether or not isolating a zone forces the auxiliary zone
output to be off - this is a single global parameter which applies to all eight zones.
┌─────────────────────────┬──────────┬─────────────────────────────┐
│
FUNCTION
│
PRESS KEY
│
COMMENTS
│
╞═════════════════════════╧══════════╧═════════════════════════════╡
│┌────────────────────────┬──────────┬────────────────────────────┐│
││
ENTER PROGRAMMING
│
PROGRAM
│
Located on Main Board
││
││
MODE
│
│
PRESS & HOLD FOR 4 BEEPS
││
││
│
│
-Zone Output Mapping
││
││
│
│
entered for "ANCIL RELAY"
││
│└────────────────────────┴──────────┴────────────────────────────┘│
│
│
│┌────────────────────────┬──────────┬────────────────────────────┐│
││
EXIT PROGRAMMING MODE
│
PROGRAM
│
Sounder on Continuously
││
││
│
│
-Select one EXIT FUNCTION:
││
│├────────────────────────┼──────────┼────────────────────────────┤│
││
1. EXIT WITHOUT
│
TEST
│
Parameters NOT changed
││
││
SAVING CHANGES
│
│
-EXITS TO NORMAL OPERATION
││
│├────────────────────────┼──────────┼────────────────────────────┤│
││
2. EXIT AND SAVE
│
SELECT
│
Parameters SAVED in EEPROM
││
││
CHANGES
│
│
with any changes made.
││
││
│
│
-EXITS TO NORMAL OPERATION
││
│├────────────────────────┼──────────┼────────────────────────────┤│
││
3. RESET TO DEFAULT
│
RESET
│
Parameters forced to default
││
││
PARAMETERS
│
│
state.
││
││
│
│
-REMAINS IN PROGRAMMING MODE
││
│└────────────────────────┴──────────┴────────────────────────────┘│
└──────────────────────────────────────────────────────────────────┘
Table 4.1
Programming Key Summary - Entering/Exiting Programming Mode
Issue 3.04
24 March 2006
Page 4-3