background image

signed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The single
sprinkler flow rate is the minimum re-
quired discharge from the most hy-
draulically demanding single sprin-
kler and, the multiple sprinkler flow
rate is the minimum required dis-
charge from each of the total
number of “design sprinklers” as
specified in NFPA 13D or NFPA 13R.

TIA 99-1 (Tentative Interim Amend-
ment) with an effective date of May
22, 2000 states that the minimum re-
quired discharge from each of the
“design sprinklers” for systems de-
signed to NFPA 13 must be calcu-
lated based on delivering a minimum
design density of 0.1 gpm/sq. ft. for
each of the listed coverage areas
shown in Table A. Consult with the
Authority Having Jurisdiction regard-
ing the application of this TIA to the
currently adopted NFPA 13.

For systems designed to NFPA 13,
13D, or 13R, consult with the local
authority having jurisdiction with re-
gard to the number of “design sprin-
klers” for sloped ceilings having a
slope greater than a 2 inch rise for a
12 inch run.

Spray Coverage Criteria.

Figure 2

and 3 provide spacing rules that
must be followed to assure that the
Model TFP1 Sprinklers will provide
their design distribution of water
spray.

Location of sprinklers with respect to
obstructions to water distribution are
to be in accordance with the obstruc-
tion rules for extended coverage pen-
dent sprinklers per the requirements
of NFPA 13.

Operational Sensitivity Criteria.

For proper operational sensitivity,
the Model TFP1 must be installed be-
neath a solid ceiling having a
smooth or textured surface.

The Model TFP1 must

NOT

be used

above or below open-gridded type
suspended ceilings; beneath soffits
or beams exceeding 3 inches in
height; or, with beams, joists, or
ducts having a height of more than 3
inches located within the sprinkler
coverage areas. Beams having a
height of more than 3 inches may be
located with their centerlines along
the boundaries separating adjacent
sprinkler coverage areas.

Cold Soldering Criteria.

Figures 2

and 3 provide the minimum spacing
requirements necessary for prevent-
ing the wetting (i.e., cold soldering)
of the heat responsive element of a
non-operated Model TFP1, which is
adjacent to one which has operated.

Heat Source Criteria.

Refer to

Figure 2-1 (Plan View)

Figure 2-2 (Plan View)

Figure 2-3 (Plan View)

Figure 2-4 (Plan View)

Figure 2-5 (Plan View)

Figure 2-6 (Plan View)

Figure 2-7 (Plan View)

Figure 2-8 (Plan View)

Figure 2

Spacing Rules Under Level Ceilings

S

=

THE LENGTH OF THE COVERAGE AREA BEING
HYDRAULICALLY CALCULATED (REF. TABLE A).

3

OBSOLETE

Summary of Contents for CENTRAL TFP1

Page 1: ...ove cited stipu lations and the varied nature of residential type architecture there will be some compartment de signs which cannot be fully sprinklered in accordance with the recommendations of NFPA 13 13D or 13R In the event of this condition consult the authorities having jurisdiction for guidance and approval It is the responsibility of the in stalling contractor to provide a copy of this docu...

Page 2: ... by firmly fastening the sprinkler system piping to the structure If the sprinkler is not properly secured in position reac tion forces resulting from sprin kler operation could alter its orien tation and its water distribution pattern The sprinkler escutcheon cannot be used to hold the sprin kler in position General Service Conditions The Model TFP1 must only be utilized in wet pipe sprinkler sys...

Page 3: ...nklers will provide their design distribution of water spray Location of sprinklers with respect to obstructions to water distribution are to be in accordance with the obstruc tion rules for extended coverage pen dent sprinklers per the requirements of NFPA 13 Operational Sensitivity Criteria For proper operational sensitivity the Model TFP1 must be installed be neath a solid ceiling having a smoo...

Page 4: ...is horizontal b the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling ridge are to be in a row which runs parallel to the ridge and the sprinklers are to be spaced a minimum of 10 feet apart d the sprinklers shown in Figures 3 1 through 3 8 are located in a plane which is perpendicula...

Page 5: ...ve the Protective Cap and then push on the Escutch eon until its flange just comes in con tact with the ceiling Do not continue to push on the Escutcheon such that it lifts a ceiling panel out of its nor mal position If the Escutcheon can not be engaged with the Sprinkler or the the Escutcheon cannot be en gaged sufficiently to contact the ceil ing relocate the sprinkler fitting as necessary Carea...

Page 6: ...terial and work manship when paid for and properly installed and maintained under nor mal use and service This warranty will expire ten 10 years from date of shipment by Tyco Fire Products No warranty is given for products or components manufactured by com panies not affiliated by ownership with Tyco Fire Products or for prod ucts and components which have been subject to misuse improper in stalla...

Page 7: ...ucting The Water Distribution Located On An Intersecting Pitched Ceiling COVERAGE AREAS a 20 x 20 c 16 x 16 b 18 x 18 d 14 x 14 12 x 12 Graph A Minimum Required Horizontal Distance Between A Sprinkler Located On A Level Ceiling And An Interesting Pitched Ceiling Without Unduly Obstructing The Water Distribution 7 O B S O L E T E ...

Page 8: ...ed At A Peak NOTES 1 UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED 2 THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES OF THE PEAK IF IT IS NOT CONTINUOUS OVER THE FULL LENGTH OF THE CEILING RIDGE Graph E Minimum Required Slant Distance Between A Ridge And A Sprinkler Without Unduly Obstructing The Water Distribution NOTE UP TO A MAXIMUM OF ONE ...

Reviews: