Operation

The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, which then allows the
sprinkler to activate and water to flow.

Design
Criteria

The Series TY-B Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM’s Loss Prevention
Data Sheets). Only the Style 10 or 40
Recessed Escutcheon, as applicable,
is to be used  for recessed pendent
installations.

Installation

The Series TY-B Sprinklers must be
installed in accordance with the follow-
ing instructions:

NOTES

Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 360°F/182°C
temperature ratings.

A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet with conse-
quent leakage or impairment of the
sprinkler.

Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.

The

Series TY-B Pendent and Up-

right Sprinklers

must be installed in

accordance with the following instruc-
tions.

Step 1.

Pendent sprinklers are to be

installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.

Step 2.

With pipe thread sealant ap-

plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.

Step 3.

Tighten the sprinkler into the

sprinkler fitting using only the W-Type
6 Sprinkler Wrench  (Ref. Figure 6),
except that an 8 or 10 inch adjustable
Crescent wrench is to be used for wax
coated sprinklers. With  reference  to
Figures 1, 2, and 3, the W-Type 7
Sprinkler Wrench or the adjustable
Crescent wrench, as applicable is to
be applied to the wrench flats.

When installing wax coated sprinklers
with the adjustable Crescent wrench,
additional care needs to be exercised
to prevent damage to the wax coating
on the sprinkler wrench flats or frame
arms and, consequently, exposure of
bare metal to the corrosive environ-
ment. The jaws of the wrench should
be opened  sufficiently wide  to pass
over the wrench flats without damag-
ing the wax coating. Before wrench
tightening the sprinkler, the jaws of the
wrench are to be adjusted to just con-
tact the sprinkler wrench flats. After
wrench tightening the sprinkler, loosen
the wrench jaws before removing the
wrench.

After installation, the sprinkler wrench
flats and frame arms must be in-

TFP151

Page 3 of 8

PLATE SEATING

ESCUTCHEON

(57,2 mm)

2-1/4"

WRENCH

(39,7 mm)

1-9/16"

FLATS

7/16" (11,1 mm)

NOMINAL

MAKE-IN

SURFACE

NPT

1/2"

2-3/16"

(55,6 mm)

SSU

DEFLECTOR

DEFLECTOR

SSP

SECTION

PENDENT

UPRIGHT

CROSS

3

1

2

5

4

6

7

**

*

*

*

FIGURE 3

STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS

8.0 K-FACTOR, 1/2 INCH NPT

1 - Frame
2 - Button

3 - Sealing

Assembly

4 - Bulb
5 - Compression

Screw

6 - Deflector

*

Temperature rating is indicated on deflector or adjacent to

orifice seat on frame.

**

Pipe thread connections per ISO 7/1 can be provided on

special request.

OBSOLETE

Summary of Contents for Gem TY-B

Page 1: ...te level version of the Series TY B Pendent Sprinkler can be obtained by utilizing the Series TY B Pendent Sprinkler in combination with the Model S2 Shield WARNINGS The Series TY B Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the standards of any ...

Page 2: ... orifice seat on frame Pipe thread connections per ISO 7 1 can be provided on special request 2 4 5 6 PENDENT CROSS SECTION 58 7 mm 2 5 16 39 7 mm 1 9 16 PLATE SEATING ESCUTCHEON 1 2 12 7 mm NOMINAL MAKE IN SURFACE 1 3 NPT 3 4 RECESSED PENDENT UPRIGHT 12 7 mm NOMINAL MAKE IN 1 2 RECESSED STYLE 40 ESCUTCHEON 57 2 mm 2 1 4 3 4 NPT DEFLECTOR SSU SSP DEFLECTOR 7 FLATS WRENCH 2 7 8 73 0 mm DIA FIGURE 2...

Page 3: ...position of the sprinkler fitting to suit The Series TY B Pendent and Up right Sprinklers must be installed in accordance with the following instruc tions Step 1 Pendent sprinklers are to be installed in the pendent position and upright sprinklers are to be installed in the upright position Step 2 With pipe thread sealant ap plied to the pipe threads hand tighten the sprinkler into the sprinkler f...

Page 4: ...orrosion Resistant Sprinklers Installed with Style 10 1 2 NPT or Style 40 3 4 NPT 3 4 Total Adjustment Recessed Escutcheon as applicable 150 F 66 C Maximum Ceiling Temperature White or Any Color Frame and Deflector only N A Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 1 2 5 WAX OVER LEAD COATED LEAD COATED WAX COATED N A 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 N A 5 6 1 2 NPT PENDENT TY...

Page 5: ...gled downward and then touch the wax stick to the rod approximately one half inch away from the area re quiring retouching The wax will melt and run down onto the sprinkler The Series TY B Recessed Pendent Sprinklers must be installed in ac cordance with the following instruc tions Step A After installing the Style 10 or 40 Mounting Plate as applicable over the sprinkler threads and with pipe TFP1...

Page 6: ...pec tions should be made so as to better determine the exact sprinkler condi tion and the long term integrity of the corrosion resistant coating as it may be affected by the corrosive conditions present The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the N...

Page 7: ...ify Specify color color coded Wax Stick for retouching specify tem perature rating temperature rated Se ries TY B Sprinklers P N specify Black for 135 F P N 56 065 1 135 Red for 155 F P N 56 065 1 155 Yellow for 175 F P N 56 065 1 175 Blue for 200 F and 286 F P N 56 065 1 286 NOTES Each wax stick is suitable for retouch ing up to twenty five sprinklers The wax used for 286 F sprinklers is the same...

Page 8: ...Page 8 of 8 TFP151 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 O B S O L E T E ...

Reviews: