background image

Std. Response - Std. Coverage
Vertical Sidewall Sprinklers
Model E, K=5.6 or 8.0

GENERAL DESCRIPTION

The Star Model E, 5.6 or 8.0 K-Factor, Vertical Sidewall
Sprinklers are standard response - standard coverage,
solder type spray sprinklers designed for use in light haz-
ard, commercial occupancies such as banks, hotels,
shopping malls, offices, etc. They are designed for instal-
lation along a wall or the side of a beam and just beneath
a smooth ceiling. Horizontal sidewall sprinklers are com-
monly used instead of pendent or upright sprinklers be-
cause of aesthetics or building construction considera-
tions, where piping across the ceiling is not desirable.

WARNINGS

The Model E Sprinklers described herein must be in-
stalled and maintained in compliance with this document,
as well as with the applicable standards of the National
Fire Protection Association, in addition to the standards
of any other authorities having jurisdiction. Failure to do
so may impair the integrity of these devices.

The owner is responsible for maintaining his fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.

OPERATION

A bronze tube sealed by a steel ball holds a fusible alloy.
The tube is compression loaded and via the tension
mechanism, the cap seals the sprinkler orifice. When the
rated temperature is reached, the alloy melts, the ball is
forced inward, and the tension mechanism releases the
cap, which then allows the sprinkler to activate and flow
water.

TECHNICAL DATA

Approvals

UL and ULC Listed. FM, LPC, NYC Approved.
(Refer to Table A. The approvals apply only to the service
conditions indicated in the Design Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1/2 or 3/4 inch NPT

Discharge Coefficient

K = 8.0 GPM/psi

1/2

(115,2 LPM/bar

1/2

)

Temperature Ratings

135°F/57°C, 165°F/74°C, 212°F/100°C, 280°F/138°C,
360°F/182°C, 400°F/204°C or 520°F/271°C
(Refer to Table A)

Finishes

Chrome Plated, Natural Brass
(Refer to Table A)

Physical Characteristics (Ref. Figure 1)

The Model E utilizes a dezincification resistant (DZR)
bronze frame with a brass deflector. The waterway is
sealed with copper gasket. The fusible assembly is con-
structed of bronze and stainless steel components.

SIN S5002

Vertical Sidewall (Shown Upright)

K=5.6, 1/2" NPT

SIN S5009

Vertical Sidewall (Shown Upright)

K=8.0, 3/4" NPT

Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500

3-01

1-1.3.30

TYCO FIRE PRODUCTS

OBSOLETE

Summary of Contents for Star E

Page 1: ... to any questions OPERATION A bronze tube sealed by a steel ball holds a fusible alloy The tube is compression loaded and via the tension mechanism the cap seals the sprinkler orifice When the rated temperature is reached the alloy melts the ball is forced inward and the tension mechanism releases the cap which then allows the sprinkler to activate and flow water TECHNICAL DATA Approvals UL and UL...

Page 2: ... with a torque of 10 to 20 ft lbs 13 6 to 27 1 Nm A maximum of 30 ft lbs 40 7 Nm of torque may be used to install sprinklers with 3 4 NPT connections Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler 1 The Model E Vertical Sidewall Sprinklers may be installed in either the pendent or upright position and the flow Ref Figure 1 or 2 is to ...

Page 3: ...d Occupancies 4 Approved by the City of New York under MEA 395 91 M TABLE A LABORATORY LISTINGS AND APPROVALS 280 F 138 C Blue 360 F 182 C Red Natural Brass Chrome Plated K 5 6 in Upright Position S5002 1 2 3 4 2 4 400 F 204 C 520 F 271 C Green Orange K 8 0 in Pendent Position S5009 SPRINKLER FINISH K 8 0 in Upright Position S5009 Temperature Rating Frame Color Code Natural Brass Chrome Plated Nat...

Page 4: ...arranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Prod ucts or for products and components which have been subject to misuse improper installation corrosion or which have not been installed maintained modified or re paired in accordance with applicable Standards of the Na tional Fire Protection Association and or the standards of any o...