Std Response - Std. Coverage
Upright and Pendent
Intermediate Level Sprinklers
Model I-LD-2
K=5.6 and 8.0

GENERAL DESCRIPTION

The Star Model I-LD-2, 5.6 and 8.0 K-Factor, Upright and
Pendent, Intermediate Level Sprinklers are standard re-
sponse - standard coverage, fusible solder type spray
sprinklers primarily designed for use in rack storage sprin-
kler systems. The Shields are intended to help prevent
water spray from higher elevation sprinklers, which could
operate earlier during a fire, from wetting the fusible ele-
ment of lower elevation sprinklers, e.g., sprinklers located
in rack storage or sprinklers located beneath open grid-
ded catwalks.

WARNINGS

The Model I-LD-2 Sprinklers described herein must be in-
stalled and maintained in compliance with this document,
as well as with the applicable standards of the National
Fire Protection Association, in addition to the standards
of any other authorities having jurisdiction. Failure to do
so may impair the integrity of these devices.

The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.

OPERATION

A bronze tube sealed by two stainless steel balls holds a
fusible alloy. When the rated temperature is reached, the
alloy melts, the balls are forced toward each other releas-
ing the tension mechanism, which then allows the sprin-
kler to activate and flow water.

TECHNICAL DATA

Approvals

UL and ULC Listed. FM and NYC Approved.
(Refer to Table A. The approvals apply only to the service
conditions indicated in the Design Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1/2 inch NPT for K=5.6
3/4 inch NPT for K=8.0

Discharge Coefficient

K = 5.6 GPM/psi

1/2

(80,7 LPM/bar

1/2

)

K = 8.0 GPM/psi

1/2

(115,2 LPM/bar

1/2

)

Temperature Ratings

135°F/57°C, 165°F/74°C, 212°F/100°C,
280°F/138°C, or 360°F/182°C
(Refer to Table A)

Finish

Sprinkler: Natural Brass

Physical Characteristics (Ref. Figure 1)

The Model I-LD-2 utilizes a dezincification resistant
(DZR) bronze frame with a brass deflector and shield.
The waterway is sealed with Teflon

†

gasketed brass but-

ton, and the fusible assembly is constructed of bronze
and stainless steel components.

†

DuPon

t

Regi

ste

red

Trad

emar

k

SIN S1809

K=5.6 Upright

With I-LD-2

SIN S1801

K=5.6 Pendent

With Separately

Ordered I-LD-2

Shield & O-Rings

SIN S1822

K=8.0 Upright

With I-LD-2 Shield

SIN S1811

K=8.0 Pendent

With Separately

Ordered I-LD-2

Shield & O-Rings

Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500

3-01

1-4.2.20

TYCO FIRE PRODUCTS

OBSOLETE

Summary of Contents for Star I-LD-2

Page 1: ...y two stainless steel balls holds a fusible alloy When the rated temperature is reached the alloy melts the balls are forced toward each other releas ing the tension mechanism which then allows the sprin kler to activate and flow water TECHNICAL DATA Approvals UL and ULC Listed FM and NYC Approved Refer to Table A The approvals apply only to the service conditions indicated in the Design Criteria ...

Page 2: ...EDIATE LEVEL SPRINKLERS NPT 1 2 2 5 8 66 7 mm MAKE IN NOMINAL 11 1 mm 7 16 68 3 mm 2 11 16 PENDENT UPRIGHT WRENCHING AREA 3 76 2 mm DIA SHIELD O RINGS FIELD ASSEMBLED SEE INSTALLATION SECTION FACTORY ASSEMBLED WRENCHING FLANGES MAKE IN NOMINAL 11 1 mm 7 16 1 2 NPT FIGURE 2 8 0 K FACTOR MODEL I LD 2 UPRIGHT AND PENDENT INTERMEDIATE LEVEL SPRINKLERS NPT 3 4 2 11 16 68 3 mm PENDENT UPRIGHT WRENCHING ...

Page 3: ...inkler wrenching area shown in Figure 1 or 2 as applicable Pendent Sprinklers The Model I LD 2 Intermediate Level Pendent Sprinklers must be installed in accordance with the following instruc tions 1 Roll one of the two required O Rings over the sprinkler threads until it seats against the sprinkler wrenching area flange as shown in Figure 1 or 2 as applicable 2 Install the Shield over the sprinkl...

Page 4: ...ed by companies not affiliated by ownership with Tyco Fire Prod ucts or for products and components which have been subject to misuse improper installation corrosion or which have not been installed maintained modified or re paired in accordance with applicable Standards of the Na tional Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found b...

Reviews: