background image

INSTALLATION

The 8.0 K-Factor, SuperNova S126 Sprinklers must be in-
stalled in accordance with the following instructions:

NOTES

A leak tight 3/4 inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs. (13,6 to 27,1 Nm).
A maximum of 30 ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers. Higher levels of torque may distort
the sprinkler inlet with consequent leakage or impairment
of the sprinkler.

Do not attempt to compensate for insufficient adjustment
in an Escutcheon Plate by under- or over-tightening the
Sprinkler. Readjust the position of the sprinkler fitting to
suit.

1. The S126 Sprinklers must be installed with their center-

line of waterway parallel to the ceiling and perpendicular

to the back wall surface. The word “TOP” on the deflec-
tor must face upwards toward the ceiling.

2. After installing an escutcheon (as applicable) over the

sprinkler pipe threads and with pipe thread sealant ap-
plied to the pipe threads, hand tighten the sprinkler into
the sprinkler fitting.

3. Wrench tighten the Sprinkler using only the W-Type 11

Sprinkler Wrench (Ref. Figure 2). The wrench recess of
the W-Type 11 is to be applied to the sprinkler wrench-
ing area (Ref. Figure 1).

STAR SPRINKLER

Page 2

1-2.3.21

TABLE A

UL AND ULC LISTING CRITERIA FOR INSTALLATION OF

8.0 K-FACTOR, SUPERNOVA S126 (SIN S1868) QR-EC HORIZONTAL SIDEWALL SPRINKLERS

Application

Coverage Area

W x  L

FT. x FT. (m x m)

Minimum

Flow

(c)

GPM (LPM)

Minimum

Pressure

(c)

PSI (BAR)

Sprinkler

Temperature Rating

°F

16 x 16 (4,9 x 4,9)

140, 165

26 (98)

10.6 (0,73)

38 (144)

22.6 (1,56)

QR-EC

(a)

16 x 18 (4,9 x 5,5)

16 x 18 (4,9 x 5,5)

13.1 (0,90)

29 (110)

NOTES:

(a) For use in QR-EC and EC Light Hazard Occupancy automatic sprinkler system applications per NFPA 13.

(b) For use in EC Light Hazard Occupancy automatic sprinkler system applications per NFPA 13.

(c) Requirement is based on minimum flow in GPM from each sprinkler. The indicated residual pressures are based on the nominal K-factor.

(d) The centerline of the sprinkler waterway (Ref. Figure 1) is located 7/16 inch (11,1 mm) below the deflector (Ref. Figure 1).

(e) Follow the requirements of NFPA 13 for spacing of the S126 Sprinklers with respect to ceiling mounted obstructions.

(f) The minimum allowable spacing along a wall between the S126 Sprinklers, to prevent cold soldering, is 10 feet (3,1 m).

(g) The maximum permitted ceiling slope per NFPA 13 is a 2 inch (50,8 mm) rise over a 12 inch (304,8 mm) horizontal run, with ceiling

sloping downwards from the wall on which the sprinkler is located.

Deflector

To Ceiling

Distance(

d)

Inches (mm)

4 to 6 (100 to 150)

Deflector Boss

To Wall

Distance

(e)

Inches (mm)

2 to 6

(50 to 150)

16 x 20 (4,9 x 6,1)

16 x 20 (4,9 x 6,1)

14 x 22 (4,3 x 6,7)

16 x 22 (4,9 x 6,7)

16 x 24 (4,9 x 7,3)

18 x 16 (5,5 x 4,9)

18 x 18 (5,5 x 5,5)

20 x 16 (6,1 x 4,9)

16 x 20 (4,9 x 6,1)

16 x 22 (4,9 x 6,7)

16 x 24 (4,9 x 7,3)

EC

(b)

34 (129)

45 (170)

37 (140)

37 (140)

44 (167)

31 (117)

33 (125)

35 (133)

45 (170)

37 (140)

44 (167)

18.1 (1,25)

31.6 (2,18)

21.4 (1,48)

21.4 (1,48)

30.3 (2,09)

15.0 (1,03)

17.0 (1,17)

19.1 (1,32)

31.6 (2,18)

21.4 (1,48)

30.3 (2,09)

4 to 6 (100 to 150)

4 to 18 (100 to 450)

4 to 6 (100 to 150)

4 to 18 (100 to 450)

4 to 6 (100 to 150)

4 to 6 (100 to 150)

4 to 6 (100 to 150)

4 to 6 (100 to 150)

4 to 6 (100 to 150)

4 to 6 (100 to 150)

4 to 18 (100 to 450)

4 to 6 (100 to 150)

4 to 6 (100 to 150)

140, 165

140, 165

140, 165

140

140, 165

140

140

140, 165

140, 165

140, 165

165

165

165

OBSOLETE

Summary of Contents for Star SuperNova S126

Page 1: ...at collector assembly is comprised of two link halves which are joined together by a thin layer of solder When the rated temperature is reached the sol der melts and the two link halves separate which then al lows the sprinkler to activate and flow water TECHNICAL DATA Approvals UL and ULC Listed FM Approved NYC Accepted MEA 188 99 E The approvals apply only to the service conditions indicated in ...

Page 2: ... 5 5 16 x 18 4 9 x 5 5 13 1 0 90 29 110 NOTES a For use in QR EC and EC Light Hazard Occupancy automatic sprinkler system applications per NFPA 13 b For use in EC Light Hazard Occupancy automatic sprinkler system applications per NFPA 13 c Requirement is based on minimum flow in GPM from each sprinkler The indicated residual pressures are based on the nominal K factor d The centerline of the sprin...

Page 3: ...mitted ceiling slope for S126 Sprinklers is a 1 inch 25 4 mm rise over a 12 inch 304 8 mm horizontal run with ceiling sloping downwards from the wall on which the sprinkler is located f The deflector boss to wall distance of 2 to 2 3 4 inches 50 to 70 mm provides a heat responsive element to wall distance of 3 4 to 1 1 2 inches 20 to 40 mm Application QR EC a Coverage Area W x L FT x FT m x m Mini...

Page 4: ...use and service This warranty will expire ten 10 years from date of shipment by Tyco Fire Products No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Prod ucts or for products and components which have been subject to misuse improper installation corrosion or which have not been installed maintained modified or re paired in accordan...

Reviews: