background image

TFP443

Page 5 of 6

Installation

The TYCO RAPID RESPONSE Series 

LFII Residential Flat-Plate Concealed 

Pendent Sprinklers must be installed in 

accordance with this section:

General Instructions

Damage to the Solder Link Element dur-

ing installation can be avoided by han-

dling the sprinkler by the Support Cup 

only; that is, do not apply pressure to the 

Solder Link Element (Figure 1).
A leak-tight 1/2 inch NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum torque of 7 to 14  

ft.-lbs. (9,5 to 19,0 Nm). Higher levels 

of torque can distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.
Do not attempt to compensate for insuf-

ficient adjustment in the Cover Plate/

Retainer Assembly by under- or over-

tightening the sprinkler. Re-adjust the 

position of the sprinkler fitting to suit.

Step 1.

 Install pendent sprinklers in 

the pendent position, with the center-

line of the sprinkler perpendicular to the 

mounting surface.

Step 2.

 Remove the Protective Cap.

Step 3.

 With pipe-thread sealant ap-

plied to the pipe threads, and using the 

W-Type 18 Wrench shown in Figure 2, 

install and tighten the Sprinkler/Sup-

port Cup Assembly into the fitting. The 

W-Type 18 Wrench accepts a 1/2 inch 

ratchet drive.

Step 4.

 Replace the Protective Cap by 

pushing it upwards until it bottoms out 

against the Support Cup. The Protec-

tive Cap helps prevent damage to the 

Deflector and Guide Pins during ceiling 

installation and/or during application of 

the finish coating of the ceiling.

NOTICE

As long as the protective Cap remains 

in place, the system is considered “Out 

Of Service”.

Step 5.

 After the ceiling has been com-

pleted with the 2-1/2 inch (63 mm) diam-

eter hole and in preparation for install-

ing the Cover Plate/Retainer Assembly, 

remove and discard the Protective Cap, 

and verify that the Deflector moves up 

and down freely.
If the sprinkler has been damaged and 

the deflector does not move up and 

down freely, replace the entire sprinkler 

assembly. Do not attempt to modify or 

repair a damaged sprinkler.

Step 6.

 Screw on the Cover Plate/Re-

tainer Assembly until its flange contacts 

the ceiling. Do not continue to screw 

on the Cover Plate/Retainer Assembly 

such that it lifts a ceiling panel out of 

its normal position.
If the Cover Plate/Retainer Assembly 

cannot be engaged with the Mounting 

Cup or the Cover Plate/Retainer Assem-

bly cannot be engaged sufficiently to 

contact the ceiling, the Sprinkler Fitting 

must be repositioned.

Care and  

Maintenance

The TYCO RAPID RESPONSE

 

Series 

LFII Residential Flat-Plate Concealed 

Pendent Sprinkler (TY2524) must be 

maintained and serviced in accordance 

with ths section:
Before closing a fire protection system 

main control valve for maintenance work 

on the fire protection system that it con-

trols, obtain permission to shut down the 

affected fire protection system from the 

proper authorities and notify all person-

nel who may be affected by this action.
Absence of a Cover Plate may delay the 

sprinkler operation in a fire situation.
The owner must assure that the sprin-

klers are not used for hanging any ob-

jects and that the sprinklers are only 

cleaned by means of gently dusting with 

a feather duster; otherwise, non-opera-

tion in the event of a fire or inadvertent 

operation may result.
When properly installed, there is a nomi-

nal 1/8 inch (3,2 mm) air gap between 

the lip of the Cover Plate and the ceil-

ing, as shown in Figure 3. This air gap 

is necessary for proper operation of the 

sprinkler by allowing heat flow from a 

fire to pass below and above the Cover 

Plate to help assure appropriate release 

of the Cover Plate in a fire situation. If the 

ceiling needs repainting after sprinkler 

installation, exercise care to ensure that 

the new paint does not seal off any of 

the air gap. Failure to do so may impair 

sprinkler operation.
Factory painted Cover Plates must not 

be repainted. They should be replaced, 

if necessary, by factory painted units. 

Non-factory applied paint may adversely 

delay or prevent sprinkler operation in 

the event of a fire.
Do not pull the Cover Plate relative to the 

Retainer. Separation may result.
Sprinklers which are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.

Automatic sprinklers must never be 

painted, plated, coated, or otherwise 

altered after leaving the factory. Modi-

fied or overheated sprinklers must be 

replaced.
Care must be exercised to avoid dam-

age to the sprinklers - before, during, 

and after installation. Sprinklers dam-

aged by dropping, striking, wrench twist/

slippage, or the like, must be replaced. 
The owner is responsible for the in-

spection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards of 

the National Fire Protection Association 

(e.g., NFPA 25), in addition to the stan-

dards of any other authorities having ju-

risdiction. Contact the installing contrac-

tor or sprinkler manufacturer regarding 

any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Reviews: