Paper roll replacement

1 Undo the two Supadrive™ screws and 

remove the printer mechanism front 
cover.

2 Pull out the paper drive spindle.
3 Pull out the paper roll retaining bar and 

slide off the old paper roll.

4 Put the new paper roll onto the paper roll 

retaining bar with the paper feeding from 
the rear.

5 Press the paper roll retaining bar back into 

its grooves.

6 Feed the paper over the paper drive spin-

dle and press the spindle back into its 
retaining grooves.

7 Feed the paper through the printer mecha-

nism front cover slot and refit the retaining 
screws. 

Ordering information

Fig. 3: Paper change
1 –Paper drive  spindle
2 –Paper roll retaining bar

1

2

Item

Order Code

Spare paper roll (pk of 5)

557.301.014

Fig. 4: Order codes 

MZX Fire alarm system 

PRN800 MX Printer

Fixing Instructions  Doc. version 3

1/4

PRN800 MX Printer

Part No. 557.202.024

The PRN800 is fitted to the front cover of the 
MX /T2000 battery housing/MX2 Expan-
sion box housing and is powered from the 
panel PSU830 Power Supply via an FB800 
fuse board. The use of a thermal printer mech-
anism ensures high reliability, only the paper 
roll requires replacement periodically.

Installation instructions

The installation instructions are as fol-
lows: 

1 Open the battery/expansion housing 

and loosen or remove the relevant 
blanking strips holding the top blank-
ing plate onto the front door. 

Fig. 1: PRN800 MX printer kit
1 –Paper feed  button

1

NOTICE

The PRN800 Printer kit is 
designed for use within the MX/
T2000 battery housing and MX2 
Expansion box housing. 

CAUTION

The printer assembly must be 
powered via a FB800 fuse board 
using a 0.5 A time delay fuse.
A free cable entry hole is required 
in both the controller and battery/
expansion housings.
Any cable runs must be protected 
by conduit or trunking.