TFP2224
Page 2 of 2
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Tel1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Note: Do not attempt to compen-
sate for insufficient adjustment in the
escutcheon plate by under or over-
tightening the nozzle. Re-adjust the
position of the nozzle fitting to suit.
Absence of an escutcheon, which is
used to cover a clearance hole, can
delay the time to nozzle operation in a
fire situation.
Care and
Maintenance
The TYCO Type ULF AM24 AQUAMIST
Nozzles must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Nozzles which are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic nozzles must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified nozzles must be replaced.
Nozzles that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the nozzle with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the nozzles - before, during,
and after installation. Nozzles damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any nozzle that has a
cracked bulb or that has lost liquid from
its bulb. (Ref. Installation Section.)
Frequent visual inspections are recom-
mended to be initially performed for
nozzles installed in potentially corro-
sive atmospheres to verify the integ-
rity of the materials of construction
and finish as they may be affected by
the corrosive conditions present for a
given installation. Thereafter, annual
inspections per applicable standards
are required, in addition to inspec-
tions required by the authority having
jurisdiction.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (e.g., NFPA 20, 25, and
750), in addition to the standards of
any other authorities having jurisdic-
tion. Contact the installing contrac-
tor or product manufacturer with any
questions.
Water-mist fixed systems should be
inspected, tested, and maintained by
a qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N.)
Type ULF AM24 AQUAMIST Nozzles
Specify: Type ULF AM24 AQUAMIST
Nozzle with (specify finish), tempera-
ture rating (specify), P/N (specify):
Natural Brass
57°C (135°F) . . . . . . . . . . . . . . . . . . 49-210-1-135
68°C (155°F) . . . . . . . . . . . . . . . . . . 49-210-1-155
79°C (175°F) . . . . . . . . . . . . . . . . . . 49-210-1-175
93°C (200°F). . . . . . . . . . . . . . . . . . 49-210-1-200
Chrome Plated
57°C (135°F) . . . . . . . . . . . . . . . . . . 49-210-9-135
68°C (155°F) . . . . . . . . . . . . . . . . . . 49-210-9-155
79°C (175°F) . . . . . . . . . . . . . . . . . . 49-210-9-175
93°C (200°F). . . . . . . . . . . . . . . . . .49-210-9-200
Signal White* (RAL9003)
57°C (135°F) . . . . . . . . . . . . . . . . . . 49-210-4-135
68°C (155°F) . . . . . . . . . . . . . . . . . . 49-210-4-155
79°C (175°F) . . . . . . . . . . . . . . . . . . 49-210-4-175
93°C (200°F). . . . . . . . . . . . . . . . . .49-210-4-200
Pure White** (RAL9010)
57°C (135°F) . . . . . . . . . . . . . . . . . . 49-210-3-135
68°C (155°F) . . . . . . . . . . . . . . . . . . 49-210-3-155
79°C (175°F) . . . . . . . . . . . . . . . . . . 49-210-3-175
93°C (200°F). . . . . . . . . . . . . . . . . .49-210-3-200
* Previously known as Bright White
** Eastern Hemisphere sales only
Nozzle Wrench
Specify: W-Type 6 Nozzle Wrench,
P/N 56-000-6-387
Escutcheon
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
*Refer to Technical Data Sheet TFP770
Temperature
Rating
Bulb Fluid
Color
57°C (135°F)
Orange
68°C (155°F)
Red
79°C (175°F)
Yellow
93°C (200°F)
Green
Diffuser
Bulb
Button
Frame
Strainer
Components:
Orifice
Insert
Ejection
Spring
Loading
Screw
Sealing
Assembly
-
-
-
-
-
-
-
-
-
2
9
8
6
7
4
5
3
1
DIFFUSER
SHAPE
WRENCH
FLATS
ESCUTCHEON
PLATE SEATING
SURFACE
1/2"
NPT
11,1 mm
(7/16")
NOMINAL
MAKE-IN
17,5 mm
(11/16")
17,5 mm
(11/16")
41,3 mm
(1-5/8")
31,0 mm
(1.22")
58,7 mm
(2-5/16")
2
1
3
6
5
7
4
9
8
WRENCH RECESS
(USE ONLY
END "A")
FIGURE 1
TYPE ULF AM24 AQUAMIST NOZZLE
NOMINAL DIMENSIONS
TABLE A
TEMPERATURE RATING
SELECTION
FIGURE 2
W-TYPE 6 NOZZLE WRENCH