2.

 

CAPACITY: 

The UPSPro  UPS-ST12 is rated at 144W load output. 

The UPS-ST24 is rated at 192W load output. The UPS –ST24 can de-
liver 288W to the load but then the power available for battery charging 
is too small, so we recommend not to exceed 192W to the load for best 
performance.

 

3.

 

VENTING: 

The enclosure is vented thru the wire feedthrus and vari-

ous hole plugs in the bottom of the enclosure. Don’t make these airtight 
with silicon

 

4.

  

BATTERY MAINTENANCE: 

The batteries used in the UPSPro sys-

tems don’t require any maintenance. They should last up to 5 years in 
normal use. 

 

5.

   

BATTERY  OVERDISCHARGE

: We  highly  recommend  hooking  all 

equipment loads to the controller voltage output. This output will discon-
nect the load if the battery voltage drops below the set voltage and this 
will protect the battery from over-discharge. If batteries get completely 
discharged  because  the  equipment  was  connected  directly  to  the  bat-

SPECIFICATIONS             

Subject to change without notice

 

 

 

UPS-ST12 

UPS-ST24 

Load Voltage (DC)

 

12V  +/-5%

 

24V  +/- 5%

 

Max Load Output

 

12A  

12A  

Min Load Output

 

1A 

1A 

Available Storage 
Capacities

 

1 battery 51Ah  600VA 

2 battery 102Ah  1200VA 

4 battery 204Ah 2400VA 

2 battery 51Ah 1200VA 

4 battery 102Ah 2400VA 

Battery Type

 

Valve Regulated Sealed 

Lead Acid /  GEL 

 

Valve Regulated Sealed 

Lead Acid /  GEL 

 

Battery Life

 

5 Years 

 

5 Years 

 

Charge Voltage

 

WET Equalize = 14.6V, 
Float = 13.2V  
GEL Equalize = 14.2V, 
Float = 13.5V  

WET Equalize = 28.8V, 
Float = 26.4V  
GEL Equalize = 28.4V, 
Float = 27V  

Over-discharge 
protection

 

10.7V  Load Off 
12.6V  Load On

 

21.5V  Load Off 
25.2V  Load On

 

VAC Input +/- 10%

 

Selector Switch 
120VAC / 240VAC , 
50/60Hz  

Selector Switch 
120VAC / 240VAC , 
50/60Hz  

VAC Input Current

 

3.5A @ 115VAC / 1.8A 
@ 240VAC  

3.5A @ 115VAC / 1.8A 
@ 240VAC  

Enclosure Type

 

Powder Coat Steel 

 

Powder Coat Steel 

 

Operating Temper-
ature

 

-30°C to +60°C  

-30°C to +60°C  

Summary of Contents for UPSPro UPS-ST12

Page 1: ...d power circuits Contact with power lines lights or power circuits may be fatal We recommend to install no closer than 20 feet to any power lines Safety For your own protection follow these safety rules Perform as many functions as possible on the ground Do not attempt to install on a rainy windy or snowy day or if there is ice or snow accumulation at the install site or if the site is wet Make su...

Page 2: ...STEP 2 Add wire feedthrus into the bottom connector plate Attach the connector plate to the bottom of the enclosure using self tapping screws provided STEP 3 Install hole plug in drain hole in bottom right corner of the en closure STEP 4 If pole mounting the enclosure assemble the pole mount kit to the back of the enclosure and mount the enclosure to a pole using the 6 hose clamps provided The enc...

Page 3: ...n be mounted to removable backplate or to a plate mounted to the door rails STEP 7 Install the batteries in the enclosure If using multiple batteries connect in parallel for 12V output or connect in series for 24V output 12V 200Ah bat tery configura tion is shown here For 12V 100Ah two batteries are connected in par allel with Plus connected to Plus and Minus connected to Mi nus For 12V 200Ah the ...

Page 4: ...nside the enclosure during an earthquake STEP 9 Set the proper voltage on the AC input of the controller by removing the metal tab and then switching the input voltage to 120VAC or 240VAC depending on your source voltage Be sure to replace the metal tab to ensure that somebody doesn t accidentally switch the voltage as this will damage the controller STEP 10 Connect the battery cables to the contr...

Page 5: ...don t tighten on a small diameter wire you can wrap some electrical tape around the wire in the seal area to increase its diameter and make a better seal The enclosure needs some small amount of venting so be sure NOT to seal all holes and feedthrus with silicon STEP 15 Make sure lid gasket is clean and free from any particles then carefully close the cover making sure that wires are clear of the ...

Page 6: ...ttery from over discharge If batteries get completely discharged because the equipment was connected directly to the bat SPECIFICATIONS Subject to change without notice UPS ST12 UPS ST24 Load Voltage DC 12V 5 24V 5 Max Load Output 12A 12A Min Load Output 1A 1A Available Storage Capacities 1 battery 51Ah 600VA 2 battery 102Ah 1200VA 4 battery 204Ah 2400VA 2 battery 51Ah 1200VA 4 battery 102Ah 2400V...

Page 7: ...nels side of pole mounts and out door rated connection cabling Solar panels have a 25 year output warranty Pole mounts and panels are designed for wind loads to 90MPH Note Solar kits require a TP SC24 8 solar controller Solar Kits 6 Hours Peak Sun 3 Hours Peak Sun TPSK24 85W 20W continuous 10W continuous TPSK24 120W 30W continuous 15W continuous TPSK24 240W 60W continuous 30W continuous TPSK24 85W...

Page 8: ... covers material and workmanship defects This warranty does not cover the following Parts requiring replacement due to improper installation misuse poor site conditions faulty power etc Lightning or weather damage Physical damage to the external internal parts Products that have been opened altered or defaced Water damage for units that were not mounted according to user manual Usage other than in...

Reviews: