 Turn on the 72V 900W AC/DC power supply. The MPPT 

charge controller will show PV input is active and the batteries will start 

charging after 1

-

2 minutes. When the AC/DC power supply is charging, 

both LED will be red and the unit fan will come on. This is normal. When 

the batteries are fully charged the 72V 900W charger will go into 

standby mode and one LED will turn green.

 

STEP 12: 

 The enclosure comes with a thermostatically (45C) con-

trolled 24/48V ventilation fan. Connect this fan directly to the batteries.

 

 

Note: Please see the MPPT solar controller user guide for addition-

al details. 

 

 

TECH CORNER

 

 

Additional Information you may find useful

 

Solar Ready: 

The system is solar ready. You may need to add a 

100V 30A blocking diode (Tycon pn 5600059) between the solar pan-

el and the PV input to avoid reverse current from the 72V AC/DC 

power supply going back into the solar panels.

 

Batteries: 

The batteries are maintenance free and should last over 5 

years in normal operation. The charge controller will automatically do 

a balance charge on the batteries periodically. 

 

Enclosure: 

 We recommend making extra keys in case the enclosure 

keys are lost. 

 

 

NOTES

 

 

Summary of Contents for UPSPro UPAL24/48-900

Page 1: ...ength Weatherproof Key Lock 24VDC or 48VDC Output 60A MPPT Battery Charge Controller 72V 900W AC DC Power Supply up to 1440Ah Battery Capacity Safety For your own protection follow these safety rules Perform as many functions as possible on the ground Do not attempt to install on a rainy windy or snowy day or if there is ice or snow accumulation at the install site or if the site is wet Make sure ...

Page 2: ...ntroller ground screw to chassis ground Qwik Install STEP 1 Prepare a foundation to provide level support for the enclo sure STEP 2 Place enclosure on the foundation Install 4 or 8 batteries in the box Batteries are heavy Be sure to have a helper Connect all batteries in series configuration for either 24VDC or 48VDC See Wiring Diagram Below ...

Page 3: ...e Brown wire is V Make sure to observe proper polarity STEP 8 Connect normal loads to the MPPT Charge Controller load output Maximum load is 30A Max If connecting an inverter or pump or motor it s best to connect directly to the batteries STEP 9 Double check connections and then re install the fuses in the battery cables You may see a spark when connecting the fuse This is normal Once the MPPT cha...

Page 4: ...onnect this fan directly to the batteries Note Please see the MPPT solar controller user guide for addition al details TECH CORNER Additional Information you may find useful Solar Ready The system is solar ready You may need to add a 100V 30A blocking diode Tycon pn 5600059 between the solar pan el and the PV input to avoid reverse current from the 72V AC DC power supply going back into the solar ...

Page 5: ...d with on off switch MaxSolar Panel Size 1600W 24V Battery 3200W 48V Battery Controller Display Status Battery Voltage Charging Voltage Charg ing Current Load Current Temp Bulk Charge 28 8V 24V Battery 57 6V 48V Battery Float Charge 27 6V 24V Battery 55 2V 48V Battery Over discharge protection 22V 24V Battery 44V 48V Battery Over discharge recovery volts 25 2V 24V Battery 50 4 48V Battery Controll...

Page 6: ...nitor WEB3 V2 Interfaces with Tycon MPPT solar control lers via RS485 using TPDIN Cable RS485 Logs data and provides remote monitoring and control over the network via Ethernet Interface Single RS485 cable interface to the MPPT solar controller Intuitive user interface and graphical setup Email Alerts SNMP compatibility Programmable functionality Additional features to expand monitoring and contro...

Page 7: ... replacement due to improper installation misuse poor site conditions faulty power etc Lightning or weather damage Physical damage to the external internal parts Products that have been opened altered or defaced Water damage Usage other than in accordance with instructions and the normal intended use Tycon Systems Inc 14641 S 800 W Suite A Bluffdale UT 84065 support tyconsystems com PH 801 432 000...

Page 8: ...8 ...

Reviews: