TECH CORNER

 

 

 

1.

CONTROLLER: 

The  controller  turns  off  power  to  the  load  at  11V 

(22V  if  24V  array)  and  reconnects  when  the  battery  reaches  12.6V 

(25.2V if 24V array). This protects battery from over-discharge and in-

creases battery life and performance. 

2. 

CAPACITY: 

With  a  typical  AP  running  4W  average.  A  single  12V 

52Ah battery should be able to provide backup power for up to 75 hours 

at room temperature. For cold temperatures the capacity is reduced by 

20-30%. 

3. 

VENTING: 

The  enclosure  is  vented  thru  the  included  PowerVent™. 

The fan is thermostatically controlled to  turn  on  when the temperature 

inside the enclosure exceeds 45C. It runs on 12V to 24VDC. 

4.

 DUAL INPUTS: 

The UPS-ST-600 can be used with AC Power alone 

or Solar Power alone or a combination of both. 

5. 

SOLAR PANEL: 

The MPPT controller used in the UPS-ST-600 can 

handle  a  maximum  panel  size  of  550W  @  12V  Battery  or  1100W  @ 

24V  Battery.  Maximum  panel  voltage  is  90V.  Do  not  exceed  40A  into 

the solar panel input of the solar controller.  

Summary of Contents for UPSPro UPS-ST-600

Page 1: ...ghts and power circuits Contact with power lines lights or power circuits may be fatal We rec ommend to install no closer than 20 feet to any power lines Safety For your own protection follow these safety rules Perform as many functions as possible on the ground Do not attempt to install on a rainy windy or snowy day or if there is ice or snow accumulation at the install site or if the site is wet...

Page 2: ...erVent plate STEP 3 Install hole plug in drain hole in bottom right corner of the en closure STEP 4 Mount the DIN rail to the door using screws provided Mount any extra equipment to the orange backplate and secure the backplate in the enclosure Note The DIN rail can also be mounted to the orange back plate or sides of enclosure if desired STEP 5 If pole mounting the enclo sure assemble the pole mo...

Page 3: ...t this cord to hardwire into the mains You can also mount conduit to the enclosure if local codes require it During operation the charger fan may run This is normal STEP 10 Mount any customer electronics to the inside of the enclo sure Connect any loads to the Solar Controller LOAD output LOAD LOAD Press red SET button to turn on off the LOAD output Note There are multiple cable gland feedthrough ...

Page 4: ...4 UPS ST12 50 600 1 Battery UPS ST24 50 600 2 Battery UPS ST24 100 600 4 Battery ...

Page 5: ...ve Regulated Sealed Lead Acid Absorbent Glass Mat AGM Battery Life 5 Years Controller Type 40A MPPT with status display and load control Overcharge Protection 14 4V 28 8V Over discharge protection 11V 22V Over discharge recovery voltage 12 6V 25 2V Controller Self Consumption 1W Enclosure Type Powder Coated Steel Enclosure External Size 24 x 15 x 14 610 x 381 x 356mm Enclosure Internal Size 23 x 1...

Page 6: ...6 ...

Page 7: ...mperature For cold temperatures the capacity is reduced by 20 30 3 VENTING The enclosure is vented thru the included PowerVent The fan is thermostatically controlled to turn on when the temperature inside the enclosure exceeds 45C It runs on 12V to 24VDC 4 DUAL INPUTS The UPS ST 600 can be used with AC Power alone or Solar Power alone or a combination of both 5 SOLAR PANEL The MPPT controller used...

Page 8: ...tery you will re duce the battery life 9 LOAD OUTPUT The LOAD output on the Solar Charge Controller is unregulated What that means is the voltage output follows the battery voltage This is typically 11 15V for a 12V system and 22 29V for a 24V system It is up to the user to make sure the connected load is compati ble with these voltages A voltage regulator can be added to provide regulated output ...

Reviews: